![SILENT KNIGHT INTELLIKNIGHT 5820XL Скачать руководство пользователя страница 132](http://html1.mh-extra.com/html/silent-knight/intelliknight-5820xl/intelliknight-5820xl_installation-manual_1271114132.webp)
IntelliKnight 5820XL Installation Manual
7-28
151137
Select Reporting Format
Select a reporting format for each account. Options are:
9. Press the
or
arrow to select the reporting format, then press
.
Events to Report
The next six options select which types of events (or event families) will be reported to this
account. (See Figure 7-11 for location of these options on the screen.) Events are reported by
zone.
10. Press the
or
arrow to select Must, Yes, or No (see Table below), then press
.
11. Repeat step 10 for all six event report options.
For each event family, select M, Y, or N.
Switch Attempts
Specify the number of times the dialer should attempt to report to this account before
switching to the next account. Range is 01-15.
12. Enter the number of switch attempts (or press the
or
arrow), then press
.
SIA
SIA format. 500 events per call.
CID
Ademco’s Contact ID format
S20
Same as SIA but limits events reported to 20 events per phone call.
Event Family
Events Included in this Family
Alarms
All alarms (Water Flow, Manual Pull, Detectors, Auxiliary Switches)
Alarm Restore
All alarm restores.
Supervisory/Trouble
All trouble and supervisory conditions and trouble and supervisory restores.
Enable/Disable Point
Enabling and disabling of input and output points.
Service/Test
Fire drill, walk test, dialer test, automatic test, all programming sessions.
System Reset
All system resets.
M(ust)
Must Report. Selecting "M" makes this a primary reporting account for this family of events. The dialer
MUST report events in this family to this account.
Selecting Must makes an account a primary reporting account. The dialer will try to report the event to
the primary account until it exceeds the "Switch Attempts" value. When the dialer has exceeded the
Switch Attempt retry limit, it will switch to a backup account (a "Can Report" or "Yes" account, see
below). If the dialer cannot report the event to any of the backup accounts, it will return to the primary
account and repeat the process until it exceeds the "Fail Attempts" value. If the Fail Attempts limit is
exceeded, an Account Trouble condition is generated and a local trouble will sound.
Y(es)
Can Report. Selecting Y makes this a backup account for this event family. The dialer will report to this
account only if it was previously unable to report the event to a Must account.
N(o)
No events in this family will ever be reported to this account.
Содержание INTELLIKNIGHT 5820XL
Страница 16: ...IntelliKnight 5820XL Installation Manual 3 4 151137 Figure 3 1 Wire Routing Example ...
Страница 24: ...IntelliKnight 5820XL Installation Manual 3 12 151137 ...
Страница 68: ...IntelliKnight 5820XL Installation Manual 4 44 151137 ...
Страница 82: ...IntelliKnight 5820XL Installation Manual 5 14 151137 ...
Страница 104: ...IntelliKnight 5820XL Installation Manual 6 22 151137 ...
Страница 148: ...IntelliKnight 5820XL Installation Manual 7 44 151137 ...
Страница 162: ...IntelliKnight 5820XL Installation Manual 8 14 151137 ...
Страница 172: ...IntelliKnight 5820XL Installation Manual 9 10 151137 ...
Страница 178: ...IntelliKnight 5820XL Installation Manual 10 6 151137 ...