Control Panel Installation
151137
4-33
4.12.2.2 Class A Inputs
You can connect conventional Class A switches, such as waterflow switches and pull stations,
directly to the Flexput circuits of the control panel.
To install a Class A switch:
1. Wire the Class A switch as shown in Figure 4-33.
2. Configure the circuit through programming (see Section 7.4).
Figure 4-33 Class A initiating Switches
Note: In programming any point that uses multiple Flexput circuits, the lowest Flexput circuit number is used to
refer to the circuit pair. For example, Figure 4-33 uses both Flexput circuit 5 and 6, so in programming it
would be referred to as point 5.
Note:
Flexput circuit 5 and 6
used as an example.
Any Flexput point pairing
could be used.
Supervised
Power Limited