![SILENT KNIGHT INTELLIKNIGHT 5820XL Скачать руководство пользователя страница 137](http://html1.mh-extra.com/html/silent-knight/intelliknight-5820xl/intelliknight-5820xl_installation-manual_1271114137.webp)
Programming
151137
7-33
7.5.2.7 Answering Machine Bypass
This option is used in conjunction with the SK Analog Fire System Editor 5590. This feature
ensures that an answering machine will not interfere with communication between the panel
and the computer. If an answering machine is used at the panel site, enable this feature; if an
answering machine is not used, disable the feature.
This option is factory-programmed as Yes (enabled).
The selection made here must match the programming for this option in the Communication
Configuration dialog box of the 5590 software. See the manual for the software (p/n 151004)
if you need more information.
13. Select Y (answering machine bypass enabled) or N (answering machine bypass disabled)
by pressing the
or
arrow, then press
.
7.5.3
Sys. Event Outputs
1. Enter the installer code.
2. Press
or
to display the installer menu.
3. Select
for Program Menu.
Display reads:
,QLWLDOL]LQJ
3OHDVHZDLW
4. From the Program Menu, select
for System Options.
5. From the System Options Menu, select
for Sys. Event Outputs.
7.5.3.1 Trouble Events
You can map certain system trouble events to an output group. To access the screen for
selecting output groups and cadence patterns for system trouble events.
6. Press
for Trouble Events. A screen similar to the one in Figure 7-13 will display. Select
a group and a cadence pattern for each event as needed for your application. The U: field
is for a user-specified trouble condition. You can program an output group and cadence
pattern for any of the following events:
Battery
Low battery condition.
Gnd Flt
Ground fault.
Phone Ln
Phone Line 1 or 2 trouble.
Account
Account trouble; cannot report to account.
Printer
Printer trouble. (Currently not supported; do not select.)
Aux Pwr
Auxiliary power trouble.
Sys Sw
Trouble with a system switch.
Group Tr
Trouble with an output group.
SBUS Com
SBUS communication trouble.
SBUS Pwr
SBUS power trouble.
SLC Loop
Trouble on the SLC loop.
AC Loss
AC power lost.
7
5
3
1
Содержание INTELLIKNIGHT 5820XL
Страница 16: ...IntelliKnight 5820XL Installation Manual 3 4 151137 Figure 3 1 Wire Routing Example ...
Страница 24: ...IntelliKnight 5820XL Installation Manual 3 12 151137 ...
Страница 68: ...IntelliKnight 5820XL Installation Manual 4 44 151137 ...
Страница 82: ...IntelliKnight 5820XL Installation Manual 5 14 151137 ...
Страница 104: ...IntelliKnight 5820XL Installation Manual 6 22 151137 ...
Страница 148: ...IntelliKnight 5820XL Installation Manual 7 44 151137 ...
Страница 162: ...IntelliKnight 5820XL Installation Manual 8 14 151137 ...
Страница 172: ...IntelliKnight 5820XL Installation Manual 9 10 151137 ...
Страница 178: ...IntelliKnight 5820XL Installation Manual 10 6 151137 ...