Programming
151137
7-21
Internal and
External
5815XL
(Continued)
SWITCH
(Continued)
PAS_ACK
Positive acknowledge switch. This switch must be used
in zones programmed as Positive Alarm Sequence (see
Table 7-2).
If an acknowledge switch closes when an alarm or
trouble condition is not already in progress, a trouble
will occur.
You must use a UL listed normally open, momentary
switch type. The switch must be rated at 5V, 100 mA
(minimum) and be used with an EOL resistor for
supervision.
ZN_AUX1
Latching
Use these switch types if you want to monitor special
zone-level conditions (such as operation of a fan or
damper).
Non Latching
ZN_AUX2
Latching
Non Latching
SYS_AUX1
Latching
Use these switch types if you want to monitor special
system-wide conditions (such as operation of a fan or
damper).
Non Latching
SYS_AUX2
Latching
Non Latching
DETECT SW
Used to monitor conventional 4-wire detectors, a
contact closure will generate a detector alarm event.
TAMPER
Latching
Performs identically to a supervisory switch, but will be
indicated as a tamper switch on the LCD annunciator.
Non Latching
NOTIF
OUTPUT PT
Select Group
Output Point, a general use notification type. Use for
driving standard notification appliances.
AUX CONST
Select Group
Use constant power for applications that require a
constant auxiliary power source. Power is always
present at Constant circuits.
AUX RESET
Select Group
Use for auxiliary power, resettable applications. See
Section 4.12.5.3 for a description of how this option
operates.
AUX DOOR
Select Group
Use for auxiliary power, door holder applications. For
example, if you were using an auxiliary power supply
for door holders, you would use this option. See Section
4.12.5.1 for a description of how this option operates.
RELAY
OUTPUT PT
Select Group
Output Point, a general use relay type. Use for
applications requiring a relay, such as fan shutdown,
elevator recall, and so on.
AUX RESET
Select Group
Use for auxiliary power, resettable applications. See
Section 4.12.5.3 for a description of how this option
operates.
AUX DOOR
Select Group
Use for auxiliary power, door holder applications. For
example, if you were using an auxiliary power supply
for door holders, you would use this option. See Section
4.12.5.1 for a description of how this option operates.
Table 7-6: Point Programming Options for 5815XL Modules
Module Type
Type
Selection
Function
Latching
Option
Comments
Содержание INTELLIKNIGHT 5820XL
Страница 16: ...IntelliKnight 5820XL Installation Manual 3 4 151137 Figure 3 1 Wire Routing Example ...
Страница 24: ...IntelliKnight 5820XL Installation Manual 3 12 151137 ...
Страница 68: ...IntelliKnight 5820XL Installation Manual 4 44 151137 ...
Страница 82: ...IntelliKnight 5820XL Installation Manual 5 14 151137 ...
Страница 104: ...IntelliKnight 5820XL Installation Manual 6 22 151137 ...
Страница 148: ...IntelliKnight 5820XL Installation Manual 7 44 151137 ...
Страница 162: ...IntelliKnight 5820XL Installation Manual 8 14 151137 ...
Страница 172: ...IntelliKnight 5820XL Installation Manual 9 10 151137 ...
Страница 178: ...IntelliKnight 5820XL Installation Manual 10 6 151137 ...