MSAC501-S(RS485)
Service mode (RS485 mode) English
MSAC501-S(RS485) · Date
01.07.2019 · Art.
No.
88115 · Mod.
status
168/19
29
Command
Length Reply
Description
Ey
2
VZxxxxxxxx>
Ê
(10byte)
Reading the position value, zero-point
value and calibration value:
xxxxxxx = decimal value
VZ = arithmetical sign (+ / -)
y = address (0 ... 4)
y = 0: position value
y = 1: zero point value (internal offset
value)
y = 2: calibration value
y = 3: results in error message
y = 4: 32bit position value of the interpo-
lation module (only with LD version)
FyVZxxxxxxx 10
>
Ê
(2byte)
Writing zero point value and calibration
value:
VZ = arithmetical sign (+ / -)
xxxxxxx = decimal value
y = address (1 ... 2)
y = 1: zero point value
y = 2: calibration value
Note:
If the baud rate has been set to
115.2 kBit/s only the ">
Ê
" character
string is output as the response.
G
1
Depending on
the resolution
set
Output of the set absolute resolution:
- 10Bit_Abs>
Ê
- 9Bit_Abs>
Ê
- 8Bit_Abs>
Ê
- 7Bit_Abs>
Ê
Hx
2
>
Ê
(2byte)
Input of the desired absolute resolution:
x = 0: 10 Bit
x = 1: 9 Bit
x = 2: 8 Bit
x = 3: 7 Bit
The set resolution is stored non-vola-
tilely.