continuously and red   

LED is on.(Fault code) 

 

Buzzer beeps once   

every second, and red 

LED is flashing. 

(Warning code) 

2.Replace the fan. 

Fault code 02 

Internal temperature of component   

is over 100℃. 

1.Check whether the air flow of the unit is blocked or   

whether the ambient temperature is too high. 

2.Check whether the thermistor plug is loose. 

Fault code 03 

Battery is over-charged. 

Restart the unit, if the error happens again, please   

return to repair center. 

The battery voltage is too high. 

Check if spec and quantity of batteries are meet   

requirements. 

Warning code 04 

The battery voltage/SOC is too low. 

1.Measure battery voltage in DC input. 

2.Check battery SOC in LCD when use Li battery. 

3.Recharge the battery. 

Fault code 05 

Output short circuited. 

Check if wiring is connected well and remove   

abnormal load. 

Fault code 06/58 

Output abnormal (Inverter voltage   

is over 150Vac or below 40Vac). 

1.Reduce the connected load. 

2. Restart the unit, if the error happens again, please   

return to repair center. 

Fault code 07 

The inverter is overload 110% and   

time is up. 

Reduce the connected load by switching off some   

equipment. 

Fault code 08 

Bus voltage is too high. 

1.If you connect to a lithum battery without 

communication, check whether the voltage points of   

the program 19 and 21 are too high for the lithum   

battery. 

2. Restart the unit, if the error happens again, please   

return to repair center. 

Fault code 09/53/57 

Internal components failed. 

Restart the unit, if the error happens again, please   

return to repair center. 

Warning code 15 

The input status is different in   

parallel system. 

Check if AC input wires of all inverters are   

connected well. 

Warning code 16 

Input phase is not correct. 

Change the input phase S and T wiring. 

Warning code 17 

The output phase not correct in   

parallel. 

1.Make sure the parallel setting are the same   

system(sigle or paralle; 3P1,3P2,3P3). 

2.Make sure all phases inverters are power on. 

Warning code 20 

Li battery can't communicate to the   

inverter. 

1.Check whether communication line is correct   

connection between inverter and battery. 

2.Check whether BMS protocol type is correct setting. 

Fault code 51 

Over current or surge. 

Restart the unit, if the error happens again, please   

return to repair center. 

Fault code 52 

Bus voltage is too low. 

Fault code 55 

Output voltage is unbalanced 

Fault code 56 

Battery is not connected well   

or fuse is burnt. 

If the battery is connected well, please return to   

repair center. 

Fault code 60 

Negative power fault 

1.

 

Check whether the AC output connected to the grid 

input. 

2.

 

Check whether Program 8 settings are the same for   

all parallel inverters 

3.

 

Check whether the current sharing cables are   

connected well in the same parallel phases. 

4.

 

Check whether all neutral wires of all parallel units   

are connected together. 

5.

 

If problem still exists, contact repair center. 

Fault code 80 

CAN fault 

1.

 

Check whether the parallel communication cables 

are connected well. 

2.

 

Check whether Program 23 settings are right for the 

parallel system.

 

3.

 

If problem still exists, contact repair center 

Fault code 81 

Host loss 

 

Note: 

To restart the inverter, all power sources need to be disconnected. After the LCD screen light is off, only use the battery to 

restart the inverter. 

 

Содержание MS6048D

Страница 1: ...tackable Solar Inverter Charger with AC Coupling User s Manual For Model MS6048D Version 2 1 PN MS604820220608 Manufacturer Information Sigineer Power Limited Email info sigineer com TEL 86 769 828176...

Страница 2: ...Bypass Control With Timer 28 2 4 14 Automatic Neutral to Ground Bonding 28 2 4 15 Lithium Battery Wakeup 28 2 4 16 Other Features 28 3 Installation 29 3 1 Location 29 3 2 Unpacking and Inspection 29 3...

Страница 3: ...ce around the inverter for air flow Make sure that the air can circulate freely around the unit A minimum air flow of 145CFM is required 1 1 3 To avoid a risk of fire and electronic shock Make sure th...

Страница 4: ...njury and damage NEVER charge a frozen battery 1 2 6 Don t install the inverter near batteries the inverter may heat battery electrolyte and cause corrosive fumes to vent and damage corrode nearby ele...

Страница 5: ...t can create an AC coupled system with grid tie inverters by paralleling the AC outputs to the loads This allows the users to easily retrofit the on grid system without removing the grid inverter The...

Страница 6: ...www sigineer com 4...

Страница 7: ...Parallel Communication Ports 10 Current Sharing Ports 11 AC Output 12 AC Input Terminal 13 USB Port connects to computer 14 AGS Dry Contact 15 Wi Fi GPRS Port 16 Battery Terminals 17 ON OFF Power Swit...

Страница 8: ...full power Hence the user should always switch on the load s after a few seconds of switching on the inverter to avoid switching on the load before the inverter is powered on This may prematurely tri...

Страница 9: ...charger will drastically reduce the charging current to zero once float voltage is reached The charging capacity will go to peak in around 3 seconds this may probably cause a generator to drop freque...

Страница 10: ...ualization voltage point the charge controller will extend the battery equalized time until battery voltage achieves battery equalization voltage If battery voltage is still lower than battery equaliz...

Страница 11: ...e 2 4 4 Power Saver There are two working statuses for the inverters Power On and Power Off When power switch is in the Unit Off position the inverter is powered off When power switch is turned to Pow...

Страница 12: ...inverter may be programmed to remain operating at full output voltage 2 4 5 Protections The MS Series inverter charger is equipped with extensive protections against various harsh situations faults T...

Страница 13: ...itor the inverter via both WiFi and USB port the RMT WiFi module can be connected via a short extension cable 2 4 7 LCD Specification Setup Press the On Off switch to turn on the unit The operation an...

Страница 14: ...of load power percentage of load Indicate overload happened Indicate short circuit happened Battery Information Indicate battery level by 0 24 25 49 50 74 and 75 100 in battery mode and charging stat...

Страница 15: ...ity power Indicates the utility charger circuit is working Indicates the DC AC inverter circuit is working These three signs indicate the output priority SOL FIRST indicates solar first BAT FIRST indi...

Страница 16: ...olar power is lost the utility will have higher priority than battery This mode can be regarded as SUB Solar Utility Battery In this mode the inverter will transfer between DC and AC as per the settin...

Страница 17: ...r is connected to a generator the generator should be more than twice the inverter nominal power Program 04 Power Saving Mode Enable Disable 04 SdS When the power saver mode is disabled the inverter w...

Страница 18: ...Lithium This setting only works when inverter communicates with lithium battery BMS built with the same protocol The program is set to LI the LCD will show a hidden program of 36 about BMS protocol t...

Страница 19: ...m 14 Charge Power Source Priority 14 CSO Solar Priority Solar energy will charge battery as the first priority Utility will charge battery only when solar energy is not available lost 14 SNU Solar and...

Страница 20: ...battery without AC output 3 If PV energy battery power and utility are all available inverter will transfer to line mode and provide output power to loads and charge the battery at the same time When...

Страница 21: ...d in program 05 this program can be set up The Equalization is banned for AGM batteries Program 44 Battery Equalization Voltage Model Default Value Resettable Range MS6048D 58 4V 48 58 4V Program 45 B...

Страница 22: ...m 00 to 23 and the lower two digits represent the time when inverter end to power the load setting range from 00 to 23 eg 2320 represents the time allows inverter to power the load is from 23 00 to th...

Страница 23: ...s The default value is 4 for 48V model and 2 for 24Vdc model 11 Maximum Utility Charging Current 10A to Max default 30A 12 DC to AC Transfer Voltage Default 46 0V 44 0V 51 2V resettable 12 DC to AC Tr...

Страница 24: ...Without BMS communication 21 Low Battery Cut Off Voltage With BMS communication 23 AC Output Mode Single Unit Operation 23 AC Output Mode Parallel in Single Phase 23 AC Output Mode Three phase 3P1 3P...

Страница 25: ...diately Disabled Default 48 Equalization Activated Immediately Enable 49 Utility charging time 50 AC output time LCD Display Setting The LCD display information will be switched in turns by pressing U...

Страница 26: ...irmware Version of Inverter PCB and MPPT PCB CPU1 040 00 b21 CPU2 041 00 b21 Time 15 20 10 December 15 2018 The LCD will display different inverter status when the up or down button is pressed The las...

Страница 27: ...energy Charging by utility Charging by PV energy No charging Fault mode Note Fault mode Errors are caused by inside circuit error or external reasons such as over temperature output short circuited a...

Страница 28: ...ies model there are two DC fans The DC fans will just the fan speed in a linear proportion according to load and charger wattage It will slow down after 1 minute when the triggering condition disappea...

Страница 29: ...in comparison to DC coupled systems in that PV power is converted directly from DC to AC instead of DC to DC to AC When it works with grid tie inverters to form an AC coupling off grid system It can...

Страница 30: ...BP doesn t have this feature it is optional for volume order at the time of production 2 4 15 Lithium Battery Wakeup Lithium ion battery will enter sleep mode when it is overdischarged When the protec...

Страница 31: ...nts before selecting where to install Do not mount the inverter on flammable construction materials Mount on a solid surface Install this inverter at eye level in order to allow the LCD display to be...

Страница 32: ...specification of AC input with single phase Model 2 units 3 units 4 units 5 units 6 units M3048BP 100A 120VAC 150A 120VAC 200A 120VAC 250A 120VAC 300A 120VAC M5000H 48BP 100A 230VAC 150A 230VAC 200A...

Страница 33: ...rformed with care due to high battery voltage in series CAUTION Do not place anything between the flat part of the inverter terminal and the ring terminal Otherwise overheating may occur CAUTION Do no...

Страница 34: ...e follow below steps to implement PV module connection 1 Remove insulation sleeve 10 mm for positive and negative conductors 2 Check correct polarity of connection cable from PV modules and PV input c...

Страница 35: ...as air conditioner are required at least 2 3 minutes to restart because it s required to have enough time to balance refrigerant gas inside of circuits If a power shortage occurs and recovers in a sho...

Страница 36: ...tly screwed to the battery terminals Connect the end of RJ45 of battery to BMS communication port of inverter The other end of RJ45 insert to battery communication port Note if you choose lithium batt...

Страница 37: ...c or create 230 400Vac three phase The M3048BP can be stacked up to 6 pcs to expand output power in 120Vac or create 120 208Vac three phase When they are stacked all the inverters will share the loads...

Страница 38: ...m 23 Commissioning Parallel in single phase Step 1 Check the following requirements before commissioning Correct wire connection Ensure all breakers in Line wires of load side are open and each Neutra...

Страница 39: ...wires of load side are open and each Neutral wires of each unit are connected together Step 2 Turn on all units and configure LCD program 23 as 3P1 3P2 and 3P3 sequentially Then shut down all units No...

Страница 40: ...ach Neutral wires of each unit are connected together Step 2 Turn on all units and configure LCD program 23 as 2P0 on phase1 units then set as 2P2 or 2P1 on phase2 units 2P0 2P1 split phase 120V 208V...

Страница 41: ...peration exists Power interruption may happen to critical devices which cannot bear transfer time 3 8 Communication with Computer The inverter can be monitored on the computer Please use the communica...

Страница 42: ...Fault Code Fault Event Icon on 01 Fan is locked 02 Over temperature 03 Battery voltage is too high 04 Battery voltage is too low 05 Output short circuited 06 Output voltage is too high 07 Overload tim...

Страница 43: ...13 Solar charger stops due to high PV voltage Beep once every second 14 Solar charger stops due to overload Beep once every second 15 Parallel input utility grid different Beep once every second 16 P...

Страница 44: ...place battery No response after power on No indication 1 The battery voltage is far too low 1 4V Cell 2 Battery polarity is connected reversed 1 Check if batteries and the wiring are connected well 2...

Страница 45: ...repair center Warning code 15 The input status is different in parallel system Check if AC input wires of all inverters are connected well Warning code 16 Input phase is not correct Change the input p...

Страница 46: ...receipt of shipment Claims not reported within this time frame will not be honored This warranty does not apply to and we will not be responsible for any defect in or damage to a the product if it has...

Страница 47: ...off Voltage Lead Acid Mode 42 0Vdc load 20 40 8Vdc 20 load 50 38 4Vdc load 50 Low DC Cut off Voltage Li Mode 42 0Vdc Low DC Warning SOC Li Mode Low DC Cut off SOC 5 Low DC Warning Return SOC Li Mode L...

Страница 48: ...40 to 140 Altitude 2000m Cold start voltage is the minimal battery voltage for the inverter to power on without PV or AC input Errors and omissions reserved Specifications in this manual are subject t...

Отзывы: