www.sigineer.com
10
Note: The minimum power of a load to take inverter out of sleep mode (Power Saver On) is 100
Watts.
When the inverter is in idle, even there is AC input power, the inverter will discharge the battery as
the LCD, relay, fans are powered by DC.
For more detailed technical information, please contact us.
In the “search sense” mode, the LED will blink and the inverter will make a ticking sound. At full output
voltage, the inverter will make a steady humming sound. When the inverter is used as an “uninterruptible”
power supply the search sense mode function should be defeated.
Exceptions
Some devices, when scanned by the load sensor, cannot be detected. Small fluorescent lights are the most
common example. (Try altering the plug polarity by turning the plug over.) Some computers and
sophisticated electronics have power supplies that do not present a load until line voltage is available. When
this occurs, each unit waits for the other to begin. To drive these loads, either a small companion load must
be used to bring the inverter out of its search mode, or the inverter may be programmed to remain operating
at full output voltage.
2.4.5 Protections
The MS Series inverter/charger is equipped with extensive protections against various harsh
situations/faults.
These protections include:
⚫
AC Input over voltage protection/AC Input low voltage protection
⚫
Low battery alarm/High battery alarm
⚫
Over temperature protection/Over load protection
⚫
Short Circuit protection (1s after fault)
⚫
Battery Polarity Reverse Protection
Users can customize whether the inverter should automatically restart or not after some of these protections.
Warning !
The below mistakes will damage the inverter permanently and must be avoided:
*Reverse the PV input polarity.
*Use any third-party accessories, communication cables on the inverter.
*Wire the AC input power to the AC output terminals.
2.4.6 Remote Monitoring
The MS Series inverter can be remotely monitored and controlled.
It supports 4 different types of remote monitoring
1.
Plug in the remote LCD panel to the RS485 port.
2.
Connects it to a computer via the USB port and monitor the inverter on the software.
3.
Plugs a Wi-Fi or GPRS module into Wi-Fi port, monitor it on a computer or cellphone APP.
4.
Connect to the RS485 port, it allows customer to monitor on their own software programmed with the