Connecting FC330A-x (K3X020)
i
for Belgium:
The control unit must be connected on a separate two-pole automatic circuit breaker with indication of power
and current rating, which must be installed in a way that it can easily be accessed and that it is located in the
near vicinity of the control unit. Type of cable VVB 2x1.5mm
2
+ 1.5mm
2
.
Control
Pluggable terminal block K1
Pluggable terminal block
K3
Pluggable terminal block K4
Pluggable terminal block K5
Horn 2
monitored
Horn 1
monitored
1
2
3
4
−
−
−
−
F5
3,01k
½
W (1%)
24V
max.0,5A
3
2
1
+
−
+
−
4
F6
0,5A/F
0,5A/F
24V
max.0,5A
Alarm contact 1
(active until reset)
1
2
3
4
NO
NC
C
NO
5
6
NC
C
max. 30V / 1A
max. 30V / 1A
Remote transmission
ALARM
1
2
3
4
+
−
NO
C
5
6
7
8
NC
+
−
NO
9
10
C
NC
F7
0,5A/F
F8
0,5A/F
Remote transmission
FAULT
24V
max.0,5A
max. 30V / 1A
max. 30V / 1A
from terminal block K8-5
24V
max.0,5A
Detail addressable line
see page 32
LED 1
LED 2
LED 3
LED 4
CONTROL
RL1
RL2
total current available for all control outputs
and 24V-power output is 1.5A
FIRE / FAULT
BELL
INPUT 0V
Terminal blocks K1 to K8 are pluggable termi-
nals AC (Mains), K9 (BATTERY) and K50
(Ext. 24V) are fixed
Alarm contact 2
(active until reset)
LED 1
LED 2
LED 3
LED 4
Details detectors see
manual FD-M
active as long as
is applied
for internal and
external use
LOOP 1
Pluggable terminal block K2.1
Addressable loop 1 or
Adressable line 1
1
2
3
4
+
−
+
−
1
2
3
4
+
−
+
−
max. 128 detectors
Pluggable terminal block K2.2
LOOP 2
front end
rear end
Addressable loop 2 or
Adressable line 2
front end
rear end
max. 32 detectors
stub
loop
K1
K2.1
K2.2
K3
K4
K5
3,01k
½
W (1%)
3,01k
/
½
W (1%)
3,01k
/
½
W (1%)
FC330A-x (K3X020)
or
2 loops or 2 stub lines for addressable Synova
® d
etectors of serie
300A and 600A