Connecting line extension card K3M020
outputs
lines 5 to 8
connection to
K3X020 connector A
lines 9 to 12
lines 13 to 16
4 spacer bolts L=25
12 EOL20
Jumper X21 – X32
(X21 = line 1, X22 = line 2 etc.)
Pos. ’bottom’ = detector series SynoLINE600 (default)
Pos. ’top’
= detector series SynoLINE300
only available with index ’c’ onwards
jumper must be either on pos. ’bottom’ or ’top’ (do not remove)
Pluggable terminal block K12
K3M020
Conventional line 5
1
2
3
4
+
−
+
−
5
6
7
8
+
−
+
−
Conventional line 6
Conventional line 7
Conventional line 8
EOL20
max. 32 detectors
EOL20
Pluggable terminal block K17
Z3B171
14
12
11
A2
A1
10A / 250V
AC
1
2
3
4
−
−
−
−
air condition-
ing control
2nd floor
max. 32 detectors
Pluggable terminal block K13
Conventional lines 9..12
1
8
...
...
Pluggable terminal block K14
Conventional lines 13..16
1
8
...
...
6
7
8
−
−
−
−
5
LINE
Example
OUTPUT
LINE
LINE
Terminal blocks K12 to K17 are pluggable
Programmable control output 9
Programmable control output 10
Programmable control output 11
Programmable control output 12
Programmable control output 13
Programmable control output 14
Programmable control output 15
Programmable control output 16
total current available for all control outputs
and 24V-power output is 1.5A
max. 48mA
Details detectors see
manual FD-M
connect to K8 / K3X020
Detail SynoLINE600
see page 33 / 110