Fire Safety & Security Products
Building Technologies
1583_o_en_−−_4
65
08.2005
4.6
Display of alarm messages
The display is divided into a lower and an upper section, of 2 lines each.
− upper section
shows the first message or serves as ’scroll box’
− lower section
always shows the last message
− indication of
’1 (4)’
means: message 1 of 4 displayed
Spontaneous display
− Upper section
first message
− Lower section
not used
− Upper section
countdown (1:29min) if
alarm organization is used
Scrolling
Scrolling becomes necessary when more than 2 alarm events have been reported.
− Upper section
1st message and scroll box
− Lower section
last message
− Upper section
if alarm organization is used
(countdown shown)
− Upper section
with alarm organization while
scrolling (countdown removed)
− Scrolling is done by pressing the ’scroll’ key
Additional information on request
− Upper section by pressing F2
device address
with timeout of 5sec
− Upper section by pressing F1
alarm type
with timeout of 5sec
zone ###/##: ######
1st floor office 101
1 (1)
Display shows 1 message
standard (user) text
user text (39 char.)
total messages
upper
lower
zone ###/##: ###### ##:##min
1st floor office 101
1 (1)
zone ###/##: ###### 1 (4)
1st floor office 101
zone ###/##: ###### 4 (4)
1st floor corridor
zone ###/##: ###### ##:##min
1st floor office 101
zone ###/##: ###### 4 (4)
1st floor corridor
zone ###/##: ###### 2 (4)
1st floor office 102
zone ###/##: ###### 4 (4)
1st floor corridor
zone ###/##: ###### 1 (4)
address: line ##, dev ###
zone ###/##: ###### 4 (4)
1st floor corridor
zone ###/##: ###### 1 (4)
> detector
zone ###/##: ###### 4 (4)
1st floor corridor