Fire Safety & Security Products
Building Technologies
1583_o_en_−−_1
2
08.2005
1.1
Features
Features
FC330A-ECO...
FC330A-x
Application range
small installations
small and medium installations
Suitable for installer market
x
x
Pre−assembled at factory
x
x
Detector loops (SynoLOOP)
1
2 + 2
Addressable Synova
®
detectors and input modules
...128
...512
5)
Addressable output modules
...64
...64
Conventional detector lines
−
4 / 12 (optional)
Programmable outputs on LON−bus
...256
...256
Programmable inputs on LON−bus
...16
...16
Programmable outputs internal
8 (+ 12)
8 (+ 12 + 8 optional)
Programmable inputs internal
4
4
Inputs for 4 spare LEDs
x
x
Monitored control lines for sounders
2 (+ 2)
2 (+ 2 + 2 optional)
Monitored control lines for remote transmission
−
2
Dry contacts
2
2 (+ 2 optional)
Serial ports
1 x RS232 / all applications
3)
2 x RS232 / all applications
3)
Remote indicator / control panels on LON−bus
..3 (..16)
1)
..16
4)
Remote output devices on LON−bus
..3 (..16)
1)
..16
4)
Logical zones for detectors/input modules
...128
...512
Logical zones for control outputs
...128
...128
Programmable alarm organization
x
x
Programmable multi−logic for detectors
x
x
System clock
− date pre-programmed until 2079
− each country with individually pre programmed holidays
− autom. summer/winter time switching for Western Europe
− clock ac/− 15 min./year
x
x
x (function to enable)
x
x
x
x (function to enable)
x
Alarm counter
x (1000)
x (1000)
Event memory storing up to 200 events
x
x
Automatic reading of detector and LON−bus network
x
x
Automatic zone allocation on startup
x
x
Optional parallel indicator panel
−
x
2)
Optional module LED−outputs for zone ALARM
−
x
Optional interface card for pager system
x
x
Optional power supply
−
x
Power supply
...50VA / ..72h
..100VA (+ ..120VA opt.) / ..72h
Supply outputs 24V
1 x 0,5A
1 x 0,5A / 1 x 1A (1 x 3.15A opt.)
Supply mode
− external 24V
− mains + external 24V
− mains without battery
− mains + battery
−
−
x
x
x
x
x
x
Available cabinet sizes
1
2
Adapter for mounting into 19” cabinet
x
−
Cabinet door lock mechanism
2 Allen screws
DOM key lock / Nordic key lock
Space for fire control relays
...4 relays
...8 relays (+ ...8 relays optional)
On site user programming
configuration tool / direct
configuration tool / direct
1) only possible with external power supply
2) only with FC330A-2/-2-CH/-5
3) Applications: ’LON-bus’ or ’printer’ or ’BMS’ (open interface to 3rd party)
4) for >8 resp. 10 use add-on power supply Z3I1000
5) limitation of 512 detectors and/or manual call points according to BS-EN54-2