![Siemens Synova FC330A Скачать руководство пользователя страница 124](http://html.mh-extra.com/html/siemens/synova-fc330a/synova-fc330a_manual_379199124.webp)
Fire Safety & Security Products
Building Technologies
1583_o_en_−−_7
120
08.2005
multiple faults on line ##
Several faults on the addressable line simultaneously.
disconnect line then re-connect section by section
NEW device > line ##
New device within the displayed line inserted.
check and adapt configuration
No resp. from LON−interface card
No communication to RS232/LON card K3I080
check connection
OPEN CIRCUIT in horn−line ##
Control line ‘horn’ either short circuit, reversed polarity or miss-
ing blocking diode to sounder(s).
check wiring of sounder(s)
OPEN CIRCUIT RT−alarm
Control line ‘remote transmission ALARM’ either short circuit,
wrong polarity or missing diode to load.
check wiring
OPEN CIRCUIT RT−fault
Control line ‘remote transmission FAULT’ either short circuit,
wrong polarity or missing diode to load.
check wiring
paperOUT/powerOFF printer (code #)
Printer disconnected or locally turned off.
reconnect or turn on printer or replace paper
then
reset fault
Power FAULT in FBF
VdS card K3L070 is out of power.
check fuse on K3L070
Power supply mismatch
Jumpers ’ST11...14’ not set correctly.
check jumpers ’ST11...14’ on K3X...
printer in mode ’off line’
Printer locally turned off or unpowered or, depending on printer
type, also run out of paper.
check printer
then
reset
read/write ERROR flash−EPROM #
Read /Write problem on FLASH−EEPROM.
restart system, if still reported replace K3X...
RESTART due to manual initiation
Normal procedure after manual restart with switch ’S1’.
reset
RESTART due to power down
System stop due to disconnection by ’low discharge protec-
tion’ (= mains failure and battery <22.5V ).
restore mains supply
reset
RESTART due to system fault
General system fault (also appears when system has been
out of order and is put back into operation again).
reset (
if this is taking place frequently
replace K3X...)
RESTART due to watchdog: Part #
Restart due to software or hardware error.
reset
(if this is taking place frequently
replace K3X...)
RESTART due to wrong CHECKSUM
Periodical test of user data is negative.
reset
(if this is taking place frequently
replace K3X...)
RESTART due to soft err. File ###
Indicates a software problem.
note ”file ###” if it occurs several times, contact the hotline
Sabotage FAULT, door open on FSD
Door at FSD open (only with VdS card).
go to location of FSD and check situation
Sequence error at LON dev. ##
Fault on the LON-bus for short time.
if frequent contact hotline
short at term A of line ##
Short circuit at the beginning of the addressable line on K3X...
check field wiring and corresponding device
short at term B of line ##
Short circuit at the end of the addressable line on K3X...
check field wiring and corresponding device
short at term A and B of line ##
Short circuit at the beginning and at the end of the addressa-
ble line K3X...
check field wiring and corresponding device
SHORT CIRCUIT > line ##
Short circuit within the indicated line.
wait until device address is displayed