Connecting line extension card K3M010
outputs
alarm contact
horns 3 and 4
lines 5 to 8
connection to
K3X020 connector A
5V supply
voltage
available
4 spacer bolts L=25
4 EOL20
2 resistors 12k
½
W
Jumper X1 – X4
(X1 = line 1, X2 = line 2 etc.)
Pos. ’left’ = detector series SynoLINE600 (default)
Pos. ’right’ = detector series SynoLINE300
only available with index ’a’ onwards
jumper must be either on pos. ’left’ or ’right’ (do not remove)
Terminal block K12
Terminal block
K13
Terminal block K14
Horn 4
monitored
Horn 3
monitored
K3M010
F1
24V
max.0,5A
Conventional line 5
1
2
3
4
+
−
+
−
5
6
7
8
+
−
+
−
Conventional line 6
Conventional line 7
Conventional line 8
EOL20
max. 32 detectors
EOL20
3
2
1
+
−
+
−
4
F2
0,5A/F
0,5A/F
24V
max.0,5A
Alarm contact 3
(active until reset)
1
2
3
4
NO
NC
C
NO
5
6
NC
C
max. 30V / 1A
max. 30V / 1A
Detail SynoLINE600
see page 33 / 110
Terminal block K17
Z3B171
14
12
11
A2
A1
10A / 250V
AC
1
2
3
4
−
−
−
−
air condition-
ing control
2nd floor
connect to K8 / K3X020
RL3
RL4
Programmable control output 9
Programmable control output 10
Programmable control output 11
Programmable control output 12
OUTPUT
max. 32 detectors
LINE
Terminal blocks K12 to K17 are pluggable
BELL
CONTROL
Alarm contact 4
(active until reset)
total current available for all control outputs
and 24V-power output is 1,5A
Example
Details detectors see
manual FD-M
max.48mA
12k
½
W
12k
½
W