Fire Safety & Security Products
Building Technologies
1583_o_en_−−_6
110
08.2005
6.4
SynoLINE300/600
Terminal block K12
K3M010 / K3M020
Conventional line x
1
2
3
4
+
−
+
−
Conventional line x
EOL20
max. 32 detectors
LINE
V
W
H
G
–
+
–
+
L
L
SynoLOOP
EOL22
max. 25 detectors
24V
DC
+
–
conventional detection line
DC1192/
CB320A
Function
Conventional lines
Function
K3M010 / 020
K3M010 / 020
DC1192 1)
CB320A 1)
jumper X1−32
pos. default
jumper X1−32
pos. option
Connectable conventional
detector series
SynoLINE600
SynoLINE300
SynoLINE600
SynoLINE300
Connecting intrinsically safe
detectors
no
yes
via safety barrier
no
Number of detectors per line
..32 2)
(KLK = max. 32)
..32 2)
(KLK = max. 32)
..25 2)
(KLK = max. 25)
..32 OP/OHxxxC
Admissible line resistance
..250
Ω
..250
Ω
..50W or
..150W or
..250W
..100
Ω
Line voltage
normal
open line
short circuit
alarm
22V
DC
±
2%
22V
DC
±
2%
<
3.5V
3.5...17.7V
DC
22V
DC
±
2%
22V
DC
±
2%
<
3.5V
3.5...17.7V
DC
20.6...22.2V
DC
17.8...23.5V
DC
19.6...21.5V
DC
>
22.3V
DC
>
23.6V
DC
>
21.6V
DC
<
4.5V
DC
<
3.5V
DC
<
3.5V
DC
4.5..17V
DC
3.5..16V
DC
3.5..16V
DC
17.8..23.5V
DC
>
23.6V
DC
<
3.5V
DC
5.5..16.7V
DC
Quiescent line current detectors
<
3.2mA
<
3.2mA
<2.5mA
<3.3mA
Alarm activation
>
9mA
>
25mA
3.5..17V
DC
4.5..16,7V
DC
Alarm indicator current
70mA limited
70mA limited
45..60mA
with AI pulse
75..90mA
with AI pulse
Mode ‘active’ alarm indicator
flashing
flashing
flashing
flashing
Detector simultaneously in alarm
max. 1
max. 3
max. 1
max. 1..2
Principle line monitoring
cut−off for 10..15ms every 30sec / fault
if line voltage drops
<
10.2V during cut
off
initiated if line voltage is
>
22.3V
DC
>
23.6V
DC
>
21.6V
DC
initiated if line voltage is
>
23V
DC
end−of−line unit
EOL20
EOL22(Ex)
Each line assigned to logical
zone
yes
yes
Installation cable
− twisted
− non twisted
recommended
acceptable
recommended
acceptable
Component to initiate ‘line alarm’
1.2k
Ω
resistor or
z−diode 5.6V
DC
470
Ω
resistor or
z−diode 5.6V
DC
(1,5W)
1.2k
Ω
resistor or
z−diode 5.6...8.2V
DC
600
Ω
or
z−diode 5.6...8.2V
DC
1) More details see detector manual
2) Details regarding loading factor (‘KLK’) see document e825