08.2005
6.7
Remote transmission outputs (RT)
Pluggable terminal block K5
Remote transmission
ALARM (fire brigade)
1
2
3
4
+
−
NO
C
5
6
7
8
NC
+
−
NO
9
10
C
NC
F7
0,5A/F
F8
0,5A/F
Remote transmission
FAULT (fire brigade)
24V
max. 30V / 1A
max. 30V / 1A
24V
external
remote transmission
equipment
max. 0,5A
max. 0,5A
FIRE/FAULT
max. 0,5A
Pluggable terminal block K5
Remote transmission
ALARM (fire brigade)
1
2
3
4
+
−
NO
C
5
6
7
8
NC
+
−
NO
9
10
C
NC
Remote transmission
FAULT (fire brigade)
max. 30V / 1A
max. 30V / 1A
FIRE/FAULT
FC330A (K3X020)
FC330A (K3X030)
internal remote
transmission
equipment
internal remote
transmission
equipment
Characteristics
For initiation of remote transmission device, either via contact or monitored control line
”Remote alarm/Remote fault” control lines
Designed for signal receiver (24V
DC
) with relay and series diode
Line active for ”Remote alarm” or ”Remote fault”
can also be used for flashing beacons
Line monitored by termination resistor 3,01k
½
W (1%)
Operating functions for ”remote transmission alarm” (via menu)
− ON/OFF switching
− Activation (test)
Programmable functions for ”remote transmission alarm”
− Detector zone (alarm) from which the RT-alarm and the contact is to be activated
− Active phase of RT-fault until ”acknowledged” or until ”reset”
Technical data
Contact rating
max. 1A/30V
DC
Nominal voltage in normal operation (line monitoring)
11..12V
Nominal voltage in active phase (alarm)
24....29V
DC
(reversed polarity)
Max. current in active phase
500mA
Line termination
resistor 3,01k
½
W (1%)