98/232
Building Technologies
Boiler Sequence Controller RMK770
CE1P3132en
HVAC Products
6 Boiler sequence management
23.04.2009
Number Text
Effect
2396
Main flow temp not reached Nonurgent, must be acknowledged, no
plant stop
Number Text
Effect
332
[Boiler seq] MBRT sensor
error
Nonurgent message; must be acknowl-
edged, no plant stop
333
Consumer return sensor
error
Nonurgent message; must be acknowl-
edged, no plant stop
Number Text
Effect
5593
Number of boilers wrong
setting
Nonurgent message; must not be ac-
knowledged
5594
Invalid lead boiler
Nonurgent message; must not be ac-
knowledged
2202
Main contr h’request mod
error
Nonurgent message; must not be ac-
knowledged, no plant stop
5591 Failure
boiler
sequence
manager
Nonurgent message; no plant stop; must
be acknowledged
5592
>1 boiler sequence man-
ager
Nonurgent message; no plant stop; must
be acknowledged
2300
>1 boiler faulty
Urgent message, must not be acknowl-
edged, no plant stop
Main flow temperature
supervision
Sensor supervision
general
Various faults