156/232
Building Technologies
Boiler Sequence Controller RMK770
CE1P3132en
HVAC Products
10 Heating circuit control
23.04.2009
G
G0
AC
2
4
V
G
G0
M D1
N2
31
21
A05
G
G0
N1
Qx3
Qx4
Qx3
Qx4
M D2
N1 RMK770
N2 Synco™200
RLU2…
Main menu > Commissioning > Extra configuration > Heating circuit > Outputs
Operating line
Adjustable values / display / remarks
Operating mode relay 1
--- / N.Q1…, etc. (free relays only) /
Assign operating mode relay
Operating mode relay 2
--- / N.Q1…, etc. (free relays only) /
Assign operating mode relay
The
Settings
menu can be used to define for each room operating mode the operating
mode relay to be energized.
Main menu > Settings > Heating circuit > Space heating
Operating line
Range
Factory setting
Comfort relay control
--- / R1 / R2 / R1+R2
---
Precomfort relay control
--- / R1 / R2 / R1+R2
---
Economy relay control
--- / R1 / R2 / R1+R2
R2
Protection relay control
--- / R1 / R2 / R1+R2
R1+R2
The factory setting is such that the digital outputs can be connected directly to the
digital inputs of the Synco™200 controller.
Since the Synco™200 controllers do not use Precomfort mode, Precomfort is switched
to Comfort. This setting can be matched to individual requirements.
The selectable values for the operating mode relays listed above under ”Settings” have
the following meaning:
Selected value
State of relay R1
State of relay R2
--- Deenergized
Deenergized
R1 Energized
Deenergized
R2 Deenergized
Energized
R1+R2 Energized
Energized
The
Outputs
menu shows the states of the operating mode relays:
Main menu > Heating circuits > Outputs
Operating line
Current state
Operating mode relay 1
Deenergized or energized
Operating mode relay 2
Deenergized or energized
Configuration of the 2
operating mode relays
Settings
Note on factory setting
Meaning of selectable
values
Display values