188/232
Building Technologies
Boiler Sequence Controller RMK770
CE1P3132en
HVAC Products
11 Data acquisition
23.04.2009
Main menu > Commissioning > Settings
or
Main menu > Settings > Data acquisition > Meter 1
(or
2
,
3
or
4
)
Operating line
Range
Factory setting
Pulse unit
Wh / kWh / MWh / kJ /
MJ / GJ / ml / l / m3 /
Heat cost unit /
No unit / BTU
kWh
Pulse valency numerator
1…9999
1
Pulse valency denominator
1…9999
1
11.3.4 Overflow
value
The overflow value ensures that the displayed readings on the connected meter and on
the RMK770 controller are identical. The value at which the meter’s display returns to 0
can be set.
Unit and decimal place depend on the unit and the format.
The overflow value can only be changed with the OCI700.1 service tool.
Main menu > Commissioning > Settings
or
Main menu > Settings > Data acquisition > Meter 1
(or
2, 3
or
4
)
Operating line
Range
Factory setting
Overflow value
0…999’999’999
99'999’999 kWh
11.3.5 Setting and resetting meter readings
In case of deviations, service staff can adjust the pulse meter reading via datapoint
"Meter reading current". This value can only be changed with the OCI700.1 service tool.
Datapoint "Reset monthly values" allows for deleting the last 15 monthly values. The
current meter reading is retained.
Main menu > Commissioning > Settings
or
Main menu > Settings > Data acquisition > Meter 1
(or
2
,
3
or
4
)
Operating line
Range
Factory setting
Reset monthly values
Yes / No
No
11.3.6 Meter
readings
Each meter shows:
•
The current reading
•
The reading per month and the date associated with the reading over the last 15
months
Main menu > Data acquisition > Meter 1
(or
2
,
3
or
4
)
Operating line
Remarks
Meter reading current
0…999’999’999
Unit
According to the configured display format
[Readout 1] date
[Readout 1] meter reading
…
[Readout 15] date
[Readout 15] meter reading
The monthly values are always stored at midnight at the end of the month.
Using datapoint “Monthly values“, the 15 monthly values can be reset or deleted on the
password level.
Pulse valency
Setting and resetting
meter readings
Display values