6 Boiler sequence management
23.04.2009
6.6.3 Frost
protection
For more detailed information, refer to subsection 7.9.9 “Frost protection for the boiler”.
Main menu > Commissioning > Settings > …
or
Main menu > Settings >
Boiler sequence manager > Limitations
Operating line
Range
Factory setting
Frost protection for the plant
On / Off
Off
Here, it can be selected whether frost protection for the plant shall act on the main
pump. For more detailed information about frost protection for the plant, refer to section
5.3 “Frost protection for the plant”.
If the temperature at the main flow temperature sensor TMnFl falls below 5 °C, a heat
request of 10 °C is generated. If the temperature at the sensor returns to a level above
7 °C, the function is deactivated. The function is active for a minimum of 5 minutes.
If the temperature at the consumer return temperature sensor TrtCo falls below 5 °C, a
heat request of 10 °C is generated. If the temperature at the sensor returns to a level
above 7 °C, the function is deactivated. The function is active for a minimum of 5 minutes.
6.7 Diagnostics
The first diagnostic choice is offered by the info pages “Boiler sequence”, “Boiler se-
quence manager”, “Temperatures” and “Boilers”.
Info page “Boiler sequence“ shows:
•
The number of boilers included in the boiler sequence
•
The current lead boiler
•
The number of boilers released (release
9
)
•
Whether the burner operates (off, first stage, second stage, modulating)
•
Whether the boiler is faulty
Boiler sequencing
Addr. no.
Release:
Burner:
Faults:
Boiler sequence manager
State
Cause
Summer operation
Number of available boilers
Boiler sequence manager
Main flow temp actual value
Main flow temp setpoint
Main return temp actual value
MBRT return temp actual value
Boiler 1
Actual value boiler temperature
Boiler temperature setpoint
State
Cause
Boiler 2
Etc.
Boiler frost protection
Plant frost protection
Frost protection for the
main flow temperature
Frost protection for the
consumer return
temperature