214/232
Building Technologies
Boiler Sequence Controller RMK770
CE1P3132en
HVAC Products
15 Fault tracing support
23.04.2009
15
Fault tracing support
If a fault is displayed, it is always practical to select the
Main menu
, operating line ”Faults
> Faults current”
,
and look for any pending fault status messages before starting to
rectify a fault. If an extension module is faulty, that fault must be corrected first because
it can lead to sub sequential fault status messages.
For a detailed description of the display, acknowledgement and resetting of faults, refer
to subsection 13.5.1 “Acknowledgement and reset“.
15.1 Fault code list
The RMK770 controller has maximum 1 heating circuit and 1 time switch. Index 1
indicates that the fault occurred on this plant.
The table below contains the fault number texts with which the controller is supplied.
Texts with designations of aggregates, such as [Boiler …], [Primary controller] and
[Heating circuit], can be changed on the password level.
Number
Name (as supplied)
For explanation, refer to section …
10
Outside temp sensor error
10.11
11
>1 outside temperature sensor
10.11
12
Outs sensor simulation active
10.11
50
[HC 1] error flow sensor
10.11
51
[HC 1] error return sensor
10.11
57
Prim controller error flow sensor
9.10
58
Prim controller error ret sensor
9.10
60
Room sensor error plant 1
10.11
61
>2 room sensors in plant 1
10.11
301
[Boiler 1] boiler sensor error
7.15
302
[Boiler 2] boiler sensor error
7.15
303
[Boiler 3] boiler sensor error
7.15
304
[Boiler 4] boiler sensor error
7.15
305
[Boiler 5] boiler sensor error
7.15
306
[Boiler 6] boiler sensor error
7.15
311
[Boiler 1] return sensor error
7.15
312
[Boiler 2] return sensor error
7.15
313
[Boiler 3] return sensor error
7.15
314
[Boiler 4] return sensor error
7.15
315
[Boiler 5] return sensor error
7.15
316
[Boiler 6] return sensor error
7.15
321
[B1] flue gas temp sensor error
7.15
322
[B2] flue gas temp sensor error
7.15
323
[B3] Flue gas temp sensor error
7.15
324
[B4] flue gas temp sensor error
7.15
325
[B5] flue gas temp sensor error
7.15
326
[B6] flue gas temp sensor error
7.15
330
Main flow sensor error
6.4
331
Main return sensor error
6.4
332
[Boiler seq] MBRT sensor error
6.4
333
Consumer return sensor error
6.4
2202
Main contr h’request mod error
6.8
2203
Prim contr h’request mod error
9.10
2300
>1 boiler faulty
6.8
2301
[B1 burner] fault
7.15
Note