10 Heating circuit control
23.04.2009
10.3.4 Timer
function
Using a configured input, the pulse triggered via a button can be acquired to extend
Comfort mode when in
mode. The timer’s time can be adjusted.
The timer function is immediately activated.
60 min
60 min
60 min
ON
OFF
A
B
C
31
40
D
0
5
A Room operating mode according to the time switch
B
Timer function
C
Resultant room operating mode
The input is activated via the extra configuration:
Main menu > Commissioning > Extra configuration > Heating circuit > Inputs > Timer function
Assign terminal
Main menu > Commissioning > Settings > …
or
Main menu > Settings > Heating circuit > Space heating
Operating line
Range
Factory setting
Timer function
0…720 min
60 min
This setting does not apply to the QAW740 room unit; in this case, the setting is made
directly on the room unit.
When activated, the timer can be stopped by changing the room operating mode (e.g.
via the room operating mode selector).
10.3.5 Room operating mode outputs
Function block outputs “Operating mode R1“ and “Operating mode R2“ enable the
resultant room operating mode of a heating circuit to be sent to 1 or 2 relays. This is
always possible; it is of no importance whether or not heating circuit control is used.
Forwarding the resultant room operating mode from relay outputs Qx of the RMK770
controller to a Synco™200 controller:
Extra configuration
Settings
Note on QAW740
Tip
Purpose
Application example