Step 8 – Connect the Cable to Junction Box(es)
a.
Connect Trunk
strain relief fitting. The trunk and drop cable requires a strain relief connector with an
opening of 1.3 cm (0.5 inches) in
diameter.
b.
Connect the TRUNK AND DROP
into additional junction boxes as
needed to transition to conduit between
smaller sub-arrays.
Refer to the wiring diagrams located in
the Appendix of this manual for more
information.
NOTE
: Wires are identified as follows: L1 is sheathed in Black, L2 is sheathed in red, L3
is sheathed in blue, Neutral is sheathed in white, and Ground is
grounding wire is used to ground the microinverters. A WEEB or continuous ground is
required in addition to this green grounding wire.
Balanced 208 VAC three phase
microinverters as shown:
NOTE
: The green wire acts as equipment ground. A continuous
Conductor (GEC) for system ground is also required as described in the next step.
208Y
THREE PHASE WIRING
120/240 or 208Y/120 VAC
SINGLE PHASE WIRING
Copyright
2011 Siemens Industry, Inc.
Connect the Cable to Junction Box(es)
and Drop cable into the AC junction box using an appropriate gland or
strain relief fitting. The trunk and drop cable requires a strain relief connector with an
opening of 1.3 cm (0.5 inches) in
TRUNK AND DROP cable
into additional junction boxes as
needed to transition to conduit between
rrays.
Refer to the wiring diagrams located in
the Appendix of this manual for more
Wires are identified as follows: L1 is sheathed in Black, L2 is sheathed in red, L3
is sheathed in blue, Neutral is sheathed in white, and Ground is sheathed in green. The
grounding wire is used to ground the microinverters. A WEEB or continuous ground is
required in addition to this green grounding wire.
Balanced 208 VAC three phase is accomplished by alternating phases between
microinverters as shown:
: The green wire acts as equipment ground. A continuous Grounding Electrode
for system ground is also required as described in the next step.
208Y/120 VAC
THREE PHASE WIRING
141-00015, Rev 01
and Drop cable into the AC junction box using an appropriate gland or
strain relief fitting. The trunk and drop cable requires a strain relief connector with an
Wires are identified as follows: L1 is sheathed in Black, L2 is sheathed in red, L3
sheathed in green. The
grounding wire is used to ground the microinverters. A WEEB or continuous ground is
es between
Grounding Electrode
for system ground is also required as described in the next step.