Step 4 – Attach the Microinverters to the Racking
a.
Mark the approximate centers of each PV module on the racking system.
b.
Evaluate the location of the microinverter
with respect to the PV module junction
box or any other obstructions.
c.
Ensure both that the micr
not interfere with the PV module frames
or stiffening brace, and that the drop
cable from the microinverter can easily
reach the connector on the
Drop cable.
DANGER
Hazardous voltage. Will cause death or serious injury.
working on this equipment.
an AC branch circuit as listed on page
microinverter AC branch circuit with a 20A maximum breaker.
WARNING
: Allow a minimum of 1.9 cm (0.75 inches) between the roof and the bottom of
the microinverter. Also allow 1.3 cm (0.50 inches) between the back of the PV modul
and the top of the inverter. Do not mount the microinverter in a location that allows long
term exposure to direct sunlight (i.e., it should be covered by the PV module).
d.
Ground the microinverters using either a continuous, unbroken grounding conductor
or approved grounding washers. If using grounding washers (e.g., WEEB) to ground
the microinverter chassis to the PV module racking, choose a grounding washer that
is approved for the racking manufacturer. Install one grounding washer per
microinverter. To
•
1/4” mounting hardware
•
5/16” mounting hardware
NOTE
: Using a power screwdriver is not recommended due to risk of galling.
Compatible grounding washer part numbers
Application Note. Installation guidelines are included in the Grounding Washer
Application Note. Refer to both documents at:
http://www.usa.siemens.com/microsolar
e.
With the silver side of the microinverter facing up and the black side facing down,
mount one microinverter at each of these locations using suitable hardware. The
indicator light on the underside of the microinverter will be facing the roof.
Copyright
2011 Siemens Industry, Inc.
Attach the Microinverters to the Racking
Mark the approximate centers of each PV module on the racking system.
Evaluate the location of the microinverter
with respect to the PV module junction
box or any other obstructions.
Ensure both that the microinverter does
not interfere with the PV module frames
or stiffening brace, and that the drop
cable from the microinverter can easily
reach the connector on the Trunk and
Hazardous voltage. Will cause death or serious injury.
Turn
working on this equipment.
Do NOT exceed the maximum number of microinverters in
an AC branch circuit as listed on page 27 of this manual. You must protect each
microinverter AC branch circuit with a 20A maximum breaker.
: Allow a minimum of 1.9 cm (0.75 inches) between the roof and the bottom of
the microinverter. Also allow 1.3 cm (0.50 inches) between the back of the PV modul
and the top of the inverter. Do not mount the microinverter in a location that allows long
term exposure to direct sunlight (i.e., it should be covered by the PV module).
Ground the microinverters using either a continuous, unbroken grounding conductor
or approved grounding washers. If using grounding washers (e.g., WEEB) to ground
the microinverter chassis to the PV module racking, choose a grounding washer that
is approved for the racking manufacturer. Install one grounding washer per
microinverter. Torque the microinverter fasteners to the values below.
1/4” mounting hardware – 45 lb-in minimum
5/16” mounting hardware – 80 lb-in minimum
: Using a power screwdriver is not recommended due to risk of galling.
Compatible grounding washer part numbers are included in the Racking Compatibility
Application Note. Installation guidelines are included in the Grounding Washer
Application Note. Refer to both documents at:
http://www.usa.siemens.com/microsolar
With the silver side of the microinverter facing up and the black side facing down,
mount one microinverter at each of these locations using suitable hardware. The
indicator light on the underside of the microinverter will be facing the roof.
141-00015, Rev 01
Mark the approximate centers of each PV module on the racking system.
Turn off Power before
Do NOT exceed the maximum number of microinverters in
ual. You must protect each
: Allow a minimum of 1.9 cm (0.75 inches) between the roof and the bottom of
the microinverter. Also allow 1.3 cm (0.50 inches) between the back of the PV module
and the top of the inverter. Do not mount the microinverter in a location that allows long-
term exposure to direct sunlight (i.e., it should be covered by the PV module).
Ground the microinverters using either a continuous, unbroken grounding conductor
or approved grounding washers. If using grounding washers (e.g., WEEB) to ground
the microinverter chassis to the PV module racking, choose a grounding washer that
is approved for the racking manufacturer. Install one grounding washer per
rque the microinverter fasteners to the values below.
: Using a power screwdriver is not recommended due to risk of galling.
are included in the Racking Compatibility
Application Note. Installation guidelines are included in the Grounding Washer
With the silver side of the microinverter facing up and the black side facing down,
mount one microinverter at each of these locations using suitable hardware. The
indicator light on the underside of the microinverter will be facing the roof.