SITRANS LG240 - Operating Instructions
44286-EN-171021
Lateral load with rod: ø 8 mm (0.315 in)
- polished
10 Nm (7.38 lbf ft)
Torque for exchangeable rod probe (in
the process fitting)
max. 4.5 Nm (3.32 lbf ft)
Torque for NPT cable glands and Conduit tubes
Ʋ Plastic housing
max. 10 Nm (7.376 lbf ft)
Ʋ Aluminium/Stainless steel housing
max. 50 Nm (36.88 lbf ft)
Input variable
Measured variable
Level of liquids
Min. dielectric constant of the medium
ε
r
≥ 1.6
Output variable
Output signal
4 … 20 mA/HART
Range of the output signal
3.8 … 20.5 mA/HART (default setting)
Fulfilled HART specification
7
Signal resolution
0.3 µA
Fault signal, current output (adjustable) Last valid measured value, ≥ 21 mA, ≤ 3.6 mA
Max. output current
21.5 mA
Starting current
≤ 10 mA for 5 ms after switching on, ≤ 3.6 mA
Load
see load under Power supply
Damping (63 % of the input variable),
adjustable
0 … 999 s
HART output values according to HART 7 (default setting)
2)
Ʋ First HART value (PV)
Linearised percentage value, level
Ʋ Second HART value (SV)
Distance to the level
Ʋ Third HART value (TV)
Measurement certainty, level
Ʋ Fourth HART value (QV)
Electronics temperature
Indication value - Display and adjustment module
3)
Ʋ Displayed value 1
Filling height Level
Ʋ Displayed value 2
Electronics temperature
Resolution, digital
< 1 mm (0.039 in)
Output variable - Additional current output
For details on the operating voltage see chapter "Voltage supply"
Output signal
4 … 20 mA (passive)
Range of the output signal
3.8 … 20.5 mA (default setting)
Signal resolution
0.3 µA
Fault signal, current output (adjustable) Last valid measured value, ≥ 21 mA, ≤ 3.6 mA
Max. output current
21.5 mA
2)
The output values can be assigned individually.
3)
The indication values can be assigned individually.
Содержание SITRANS LG240
Страница 2: ...2 PBD 51041038 SITRANS LG240 Operating Instructions 44286 EN 171021 ...
Страница 85: ...Notes 85 PBD 51041038 SITRANS LG240 Operating Instructions 44286 EN 171021 ...
Страница 86: ...Notes 86 PBD 51041038 SITRANS LG240 Operating Instructions 44286 EN 171021 ...
Страница 87: ...Notes 87 PBD 51041038 SITRANS LG240 Operating Instructions 44286 EN 171021 ...