![Siemens SITRANS LG240 Скачать руководство пользователя страница 57](http://html.mh-extra.com/html/siemens/sitrans-lg240/sitrans-lg240_operating-instructions-manual_374496057.webp)
57
PBD-51041038
SITRANS LG240 - Operating Instructions
44286-EN-171021
Code
Text mes-
sage
Cause
Rectification
DevSpec State in CMD 48
F264
Installation/
Setup error
•
Error during setup
•
Check for correct mounting
and/or parameter settings
•
Check probe length
Bit 10 of Byte 0 … 5
F265
Measurement
function dis-
turbed
•
Sensor no longer carries out
a measurement
•
Carry out a reset
•
Disconnect operating voltage
briefly
Bit 11 of Byte 0 … 5
F267
No executable
sensor soft-
ware
•
Sensor cannot start
•
Exchanging the electronics
•
Send instrument for repair
No communication possible
The following table shows the error codes and text messages in the
status message "
Function check
" and provides information on causes
as well as corrective measures.
Code
Text mes-
sage
Cause
Rectification
DevSpec
State in CMD 48
C700
Simulation ac-
tive
•
A simulation is active
•
Finish simulation
•
Wait for the automatic end
after 60 mins.
"Simulation Active" in "Stand-
ardized Status 0"
The following table shows the error codes and text messages in the
status message "
Out of specification
" and provides information on
causes as well as corrective measures.
Code
Text mes-
sage
Cause
Rectification
DevSpec State in CMD 48
S600
Impermissi-
ble electronics
temperature
•
Temperature of the process-
ing electronics in the non-
specified section
•
Check ambient temperature
•
Insulate electronics
•
Use instrument with higher
temperature range
Bit 8 of Byte 14 … 24
S601
Overfilling
•
Level echo in the close range
not available
•
Reduce level
•
100 % adjustment: Increase
value
•
Check mounting socket
•
Remove possible interfering
signals in the close range
•
Use coaxial probe
Bit 9 of Byte 14 … 24
S602
Level with-
in the search
range, com-
pensation
echo
•
Compensation echo super-
imposed by medium
•
100 % adjustment: Increase
value
Bit 10 of Byte 14 … 24
Function check
Out of specification
Содержание SITRANS LG240
Страница 2: ...2 PBD 51041038 SITRANS LG240 Operating Instructions 44286 EN 171021 ...
Страница 85: ...Notes 85 PBD 51041038 SITRANS LG240 Operating Instructions 44286 EN 171021 ...
Страница 86: ...Notes 86 PBD 51041038 SITRANS LG240 Operating Instructions 44286 EN 171021 ...
Страница 87: ...Notes 87 PBD 51041038 SITRANS LG240 Operating Instructions 44286 EN 171021 ...