![Siemens SITRANS LG240 Скачать руководство пользователя страница 55](http://html.mh-extra.com/html/siemens/sitrans-lg240/sitrans-lg240_operating-instructions-manual_374496055.webp)
55
PBD-51041038
SITRANS LG240 - Operating Instructions
44286-EN-171021
•
Display and adjustment module
Further echo curves:
Up to 10 echo curves can be stored in a ring
buffer in this memory section. Additional echo curves are stored via:
•
PC with PACTware/DTM
•
Control system with EDD
•
Display and adjustment module
9.3 Status messages
The instrument features self-monitoring and diagnostics according to
NE 107 and VDI/VDE 2650. In addition to the status messages in the
following tables, detailed error messages are available under menu
item "
Diagnostics
" via the display and adjustment module, PACTware/
DTM and EDD.
The status messages are divided into the following categories:
•
Failure
•
Function check
•
Out of specification
•
Maintenance requirement
and explained by pictographs:
4
1
2
3
Fig. 26: Pictographs of the status messages
1 Failure - red
2 Out of specification - yellow
3 Function check - orange
4 Maintenance - blue
Failure:
Due to a malfunction in the instrument, a fault message is
outputted.
This status message is always active. It cannot be deactivated by the
user.
Function check:
The instrument is being worked on, the measured
value is temporarily invalid (for example during simulation).
This status message is inactive by default. It can be activated by the
user via PACTware/DTM or EDD.
Out of specification:
The measured value is unreliable because an
instrument specification was exceeded (e.g. electronics temperature).
This status message is inactive by default. It can be activated by the
user via PACTware/DTM or EDD.
Maintenance:
Due to external influences, the instrument function
is limited. The measurement is affected, but the measured value is
still valid. Plan in maintenance for the instrument because a failure is
expected in the near future (e.g. due to buildup).
Status messages
Содержание SITRANS LG240
Страница 2: ...2 PBD 51041038 SITRANS LG240 Operating Instructions 44286 EN 171021 ...
Страница 85: ...Notes 85 PBD 51041038 SITRANS LG240 Operating Instructions 44286 EN 171021 ...
Страница 86: ...Notes 86 PBD 51041038 SITRANS LG240 Operating Instructions 44286 EN 171021 ...
Страница 87: ...Notes 87 PBD 51041038 SITRANS LG240 Operating Instructions 44286 EN 171021 ...