10
PBD-51041038
SITRANS LG240 - Operating Instructions
44286-EN-171021
TS
d1
h1
h2
d2
1
L2
L1
L3
Fig. 3: Interface measurement
1 Sensor reference plane (seal surface of the process fitting)
d1 Distance to the interface
d2 Distance to the level
TS Thickness of the upper medium (d1 - d2)
h1 Height - Interface
h2 Height - Level
L1 Lower medium
L2 Upper medium
L3 Gas phase
Upper medium (L2)
•
The upper medium must not be conductive
•
The dielectric constant of the upper medium or the actual distance
to the interface must be known (input required). Min. dielectric con-
stant: 1.6. You can find a list of dielectric constants on our home
page: www.siemens.com/sitranslg.
•
The composition of the upper medium must be stable, no varying
products or mixtures
•
The upper medium must be homogeneous, no stratifications
within the medium
•
Min. thickness of the upper medium 50 mm (1.97 in)
•
Clear separation from the lower medium, emulsion phase or detri-
tus layer max. 50 mm (1.97 in)
•
If possible, no foam on the surface
Lower medium (L1)
•
The dielectric constant must be 10 higher than the dielectric
constant of the upper medium, preferably electrically conductive.
Example: upper medium dielectric constant 2, lower medium at
least dielectric constant 12.
Gas phase (L3)
•
Air or gas mixture
•
Gas phase - dependent on the application, gas phase does not
always exist (d2 = 0)
Prerequisites for inter-
face measurement
Содержание SITRANS LG240
Страница 2: ...2 PBD 51041038 SITRANS LG240 Operating Instructions 44286 EN 171021 ...
Страница 85: ...Notes 85 PBD 51041038 SITRANS LG240 Operating Instructions 44286 EN 171021 ...
Страница 86: ...Notes 86 PBD 51041038 SITRANS LG240 Operating Instructions 44286 EN 171021 ...
Страница 87: ...Notes 87 PBD 51041038 SITRANS LG240 Operating Instructions 44286 EN 171021 ...