background image

 

Applications 

 

9.5 Protection against short-time voltage dips 

SITOP PSU100S 
Operating Instructions, 02.2013, C98130-A7589-A1-3-7629 

65

 

9.5

 

Protection against short-time voltage dips 

For a drop in the line-side supply voltage, the SITOP PSU100S power supply still maintains 

the output voltage for a short time in the millisecond range (see Chapter Technical data 

(Page 39)). 
For line supplies that manifest frequent brief voltage dips, in order to increase the power 

supply reliability, it may make sense to increase the line buffering time in the device using an 

additional SITOP PSE201M buffer module. 
The SITOP PSE201M buffer module, based on electrolytic capacitors, is connected in 

parallel to the 24 V power supply output (Figure 9-5 Buffering brief power failures using the 

SITOP PSE201M buffer module (Page 65)). The buffer time is 200 ms at 40 A up to 1.6 s for 

a load current of 5 A. This time can be increased a multiple number of times by connecting 

buffer modules in parallel; the maximum buffer time is 10 s. 
You can find additional information at: 
SITOP PSE201M manual (

3RZHUVXSSO\

%XIIHUPRGXOH

'&9

 

Figure 9-5 

Buffering brief power failures using the SITOP PSE201M buffer module 

Содержание SITOP PSU100S

Страница 1: ...OP PSU100S 24 V 2 5 A 6EP1332 2BA20 SITOP PSU100S 24 V 5 A 6EP1333 2BA20 SITOP PSU100S 24 V 10 A 6EP1334 2BA20 SITOP PSU100S 24 V 20 A 6EP1336 2BA10 SITOP PSU100S 12 V 7 A 6EP1322 2BA00 SITOP PSU100S 12 V 14 A 6EP1323 2BA00 02 2013 C98130 A7589 A1 3 7629 Overview Safety instructions 1 Description device design dimension drawing 2 Mounting removal 3 Mounting position mounting clearances 4 Installat...

Страница 2: ...ated only by personnel qualified for the specific task in accordance with the relevant documentation in particular its warning notices and safety instructions Qualified personnel are those who based on their training and experience are capable of identifying risks and avoiding potential hazards when working with these products systems Proper use of Siemens products Note the following WARNING Sieme...

Страница 3: ...de range input which allows them to be connected to almost any 1 phase line supply around the world Output voltage can be adjusted in the range 22 2 24 28 V or 11 5 15 5 V Brief overload capability of 150 for 5 s min extra power Continuous overload capability of 120 up to an ambient temperature of 45 C Integrated signaling contact for 24 V OK or 12 V OK Ambient temperature 10 0 70 C To increase th...

Страница 4: ...0 230 V AC input 24 V 5 A DC output 6EP1333 2BA20 1 phase 120 230 V AC input 24 V 10 A DC output 6EP1334 2BA20 1 phase 120 230 V AC input 24 V 20 A DC output 6EP1336 2BA10 1 phase 120 230 V AC input 12 V 7 A DC output 6EP1322 2BA00 1 phase 120 230 V AC input 12 V 14 A DC output 6EP1323 2BA00 Accessories Item Order number Device identification labels 10 mm 7 mm pastel turquoise 3RT1900 1SB10 Device...

Страница 5: ...removal 17 4 Mounting position mounting clearances 19 4 1 Standard mounting position 19 4 2 Other mounting positions 22 4 2 1 6EP1332 2BA20 22 4 2 2 6EP1333 2BA20 24 4 2 3 6EP1334 2BA20 26 4 2 4 6EP1336 2BA10 28 4 2 5 6EP1322 2BA00 30 4 2 6 6EP1323 2BA00 32 5 Installation 35 5 1 Line side connection 35 5 2 Output side connection 37 6 Technical data 39 6 1 Input 39 6 2 Output 41 6 3 Efficiency 47 6...

Страница 6: ...ns 59 9 Applications 61 9 1 Parallel connection to increase power rating 61 9 2 Parallel connection for redundancy 62 9 3 Series connection for increased voltage 63 9 4 Overload protection in the 24 V output circuit 64 9 5 Protection against short time voltage dips 65 9 6 Protecting against longer power failures 66 10 Environment 69 11 Service Support 71 ...

Страница 7: ...s physical injury as well as extensive property damage Only appropriately qualified personnel may work on or in the vicinity of this equipment Perfect safe and reliable operation of this equipment is dependent on proper transportation storage installation and mounting Before installation or maintenance work can begin the system s main switch must be switched off and measures taken to prevent it be...

Страница 8: ...Safety instructions SITOP PSU100S 8 Operating Instructions 02 2013 C98130 A7589 A1 3 7629 ...

Страница 9: ...e that can be set via a potentiometer is available at the output of the device The output of the device is isolated no load proof and short circuit proof The LED display indicates the operating status The operating state of the device can be processed via the signaling contact Line input DC output Signaling contacts Potentiometer 22 2 28 24 28 V 11 5 15 5 V Indicator light output voltage OK DIN ra...

Страница 10: ...ion Page 35 The operating state of the device can be processed via the signaling contact function and contact rating see Chapter Status displays and signaling Page 12 Connections and terminal designations Line input L1 N PE One screw terminal each Output 2 screw terminals Output 2 screw terminals signal 13 14 One screw terminal each 1P 6 6 3 3 PP PP 1P PP 6 6 3 3 PD ෘ PP 1P Figure 2 2 Terminal dat...

Страница 11: ...ting Adjustment range 6EP1322 2BA00 6EP1323 2BA00 12 V 11 5 15 5 V 6EP1332 2BA20 6EP1333 2BA20 6EP1334 2BA20 24 V 22 2 28 V 6EP1336 2BA10 24 V 24 28 V NOTICE Thermal overload possible When setting the output voltage to higher than the rated voltage the output current must be derated or the permissible ambient temperature must be taken into consideration Note It is only permissible to use an insula...

Страница 12: ...SOH 3 3 3 3 3 Figure 2 5 Status displays and signaling Signaling 6EP1322 2BA00 6EP1323 2BA00 6EP1332 2BA20 6EP1333 2BA20 6EP1334 2BA20 6EP1336 2BA10 LED lights up green Signaling contact contacts 13 14 closed Normal operation Output voltage 10 V 0 5 V Normal operation Output voltage 20 V 0 5 V Normal operation Output voltage 20 V 0 5 V LED dark Signaling contact contacts 13 14 open inactive positi...

Страница 13: ...ROOHU 2YHUYROWDJH SURWHFWLRQ 7HPSHUDWXUH PRQLWRULQJ 8VHU QWHUIDFH 0RQLWRULQJ FLUFXLW 7HPSHUDWXUH 2YHUYROWDJH 3XOVH ZLGWK OLPLWLQJ QSXW WHUPLQDO QUXVK FXUUHQW OLPLWHU 5HFWLILHU LOWHU 5HFWLILHU 6HFRQGDU 2XWSXW ILOWHU 2XWSXW WHUPLQDO 0LFURFRQWUROOHU HKDYLRU ZLWK UHVSHFW WR WLPH WUD 3RZHU 2XWSXW FXUUHQW OLPLWLQJ DV D IXQFWLRQ RI WKH WHPSHUDWXUH ULYHUV 2QO IRU 3 9 2 9 2 9 2 9 2 867 9 9 9 Figure 2 6 Blo...

Страница 14: ...ons and weight SITOP PSU100S 14 Operating Instructions 02 2013 C98130 A7589 A1 3 7629 2 6 Dimensions and weight 120 126 5 32 5 125 79 8 Figure 2 7 Dimension drawing 6EP1332 2BA20 120 126 5 125 79 8 50 Figure 2 8 Dimension drawing 6EP1333 2BA20 6EP1322 2BA00 ...

Страница 15: ...5 120 126 5 125 79 8 70 Figure 2 9 Dimension drawing 6EP1334 2BA20 6EP1323 2BA00 Figure 2 10 Dimension drawing 6EP1336 2BA10 6EP1332 2BA20 6EP1333 2BA20 6EP1322 2BA00 6EP1334 2BA20 6EP1323 2BA00 6EP1336 2BA10 Dimensions W H D in mm 32 5 125 120 50 125 120 70 125 120 115 145 150 Weight Approx 0 3 kg Approx 0 4 kg Approx 0 7 kg Approx 2 4 kg ...

Страница 16: ...Description device design dimension drawing 2 6 Dimensions and weight SITOP PSU100S 16 Operating Instructions 02 2013 C98130 A7589 A1 3 7629 ...

Страница 17: ...il EN 60715 35 7 5 15 for installation in a control cabinet Mounting To mount the device position it with the mounting rail guide at the upper edge of the standard mounting rail and press down to lock it into place If this is too difficult press slider at the same time as described under Removal Removal To remove pull up the slider using a screwdriver and disengage the device at the bottom edge of...

Страница 18: ...ating Instructions 02 2013 C98130 A7589 A1 3 7629 WARNING Use in hazardous zones If the device is to be used in a hazardous zone Ex II 3G Ex nA nC IIC T4 Gc it must be installed in a distributor box with degree of protection IP54 or higher ...

Страница 19: ...f at least 50 mm should be maintained above and below the device maximum depth of the cable duct 50 mm No space is required at the side Output current as a function of the ambient temperature and mounting height SITOP PSU100S IN OUT 70 2 0 0 2 5 1 0 0 5 1 5 0 20 40 60 10 30 50 3 0 120 V 230 V 2XWSXW FXUUHQW 7HPSHUDWXUH r Figure 4 1 6EP1332 2BA20 Output current in the standard mounting position 70 ...

Страница 20: ...DWXUH r Figure 4 3 6EP1334 2BA20 Output current in the standard mounting position 70 16 0 20 8 4 12 0 20 40 60 10 30 50 24 120 V 230 V OUT SITOP PSU100S IN 2XWSXW FXUUHQW 7HPSHUDWXUH r Figure 4 4 6EP1336 2BA10 Output current in the standard mounting position SITOP PSU100S IN OUT 70 0 0 20 40 60 10 30 50 120 V 230 V 4 5 2 1 3 6 7 8 2XWSXW FXUUHQW 7HPSHUDWXUH r Figure 4 5 6EP1322 2BA00 Output curren...

Страница 21: ...0 0 0 20 40 60 10 30 50 120 V 230 V 8 10 4 2 6 12 14 16 SITOP PSU100S IN OUT 2XWSXW FXUUHQW 7HPSHUDWXUH r Figure 4 6 6EP1323 2BA00 Output current in the standard mounting position 100 60 110 80 70 90 1000 1000 3000 0 2000 4000 2XWSXW FXUUHQW 0RXQWLQJ KHLJKW P Figure 4 7 Mounting height derating Details see chapter Ambient conditions Page 59 ...

Страница 22: ...that deviate from the standard mounting position reduced mechanical resistance of the devices against vibration and shock must be expected Particularly when installing on a vertically fastened standard mounting rail additional measures may be required e g to prevent the device from slipping on the standard mounting rail 4 2 1 6EP1332 2BA20 70 2 0 0 2 5 1 0 0 5 1 5 0 20 40 60 10 30 50 3 0 120 V 230...

Страница 23: ...5 0 20 40 60 10 30 50 3 0 120 V 230 V SITOP PSU100S IN OUT 2XWSXW FXUUHQW 7HPSHUDWXUH r Figure 4 10 Mounting position 3 70 2 0 0 2 5 1 0 0 5 1 5 0 20 40 60 10 30 50 3 0 120 V 230 V 2XWSXW FXUUHQW 7HPSHUDWXUH r Figure 4 11 Mounting position 4 70 2 0 0 2 5 1 0 0 5 1 5 0 20 40 60 10 30 50 3 0 120 V 230 V 2XWSXW FXUUHQW 7HPSHUDWXUH r Figure 4 12 Mounting position 5 ...

Страница 24: ... 20 40 60 10 30 50 6 120 V 230 V SITOP PSU100S IN OUT 2XWSXW FXUUHQW 7HPSHUDWXUH r Figure 4 13 Mounting position 1 70 4 0 5 2 1 3 0 20 40 60 10 30 50 6 120 V 230 V SITOP PSU100S IN OUT 2XWSXW FXUUHQW 7HPSHUDWXUH r Figure 4 14 Mounting position 2 70 4 0 5 2 1 3 0 20 40 60 10 30 50 6 120 V 230 V SITOP PSU100S IN OUT 2XWSXW FXUUHQW 7HPSHUDWXUH r Figure 4 15 Mounting position 3 ...

Страница 25: ...0S Operating Instructions 02 2013 C98130 A7589 A1 3 7629 25 70 4 0 5 2 1 3 0 20 40 60 10 30 50 6 120 V 230 V 2XWSXW FXUUHQW 7HPSHUDWXUH r Figure 4 16 Mounting position 4 70 4 0 5 2 1 3 0 20 40 60 10 30 50 6 120 V 230 V 2XWSXW FXUUHQW 7HPSHUDWXUH r Figure 4 17 Mounting position 5 ...

Страница 26: ...T 70 8 0 10 4 2 6 0 20 40 60 10 30 50 12 120 V 230 V 2XWSXW FXUUHQW 7HPSHUDWXUH r Figure 4 18 Mounting position 1 SITOP PSU100S IN OUT 70 8 0 10 4 2 6 0 20 40 60 10 30 50 12 120 V 230 V 2XWSXW FXUUHQW 7HPSHUDWXUH r Figure 4 19 Mounting position 2 SITOP PSU100S IN OUT 70 8 0 10 4 2 6 0 20 40 60 10 30 50 12 120 V 230 V 2XWSXW FXUUHQW 7HPSHUDWXUH r Figure 4 20 Mounting position 3 ...

Страница 27: ... Operating Instructions 02 2013 C98130 A7589 A1 3 7629 27 70 8 0 10 4 2 6 0 20 40 60 10 30 50 12 120 V 230 V 2XWSXW FXUUHQW 7HPSHUDWXUH r Figure 4 21 Mounting position 4 70 8 0 10 4 2 6 0 20 40 60 10 30 50 12 120 V 230 V 2XWSXW FXUUHQW 7HPSHUDWXUH r Figure 4 22 Mounting position 5 ...

Страница 28: ... 40 60 10 30 50 24 120 V 230 V OUT SITOP PSU100S IN 2XWSXW FXUUHQW 7HPSHUDWXUH r Figure 4 23 Mounting position 1 70 16 0 20 8 4 12 0 20 40 60 10 30 50 24 120 V 230 V OUT SITOP PSU100S IN 2XWSXW FXUUHQW 7HPSHUDWXUH r Figure 4 24 Mounting position 2 70 16 0 20 8 4 12 0 20 40 60 10 30 50 24 120 V 230 V OUT SITOP PSU100S IN 2XWSXW FXUUHQW 7HPSHUDWXUH r Figure 4 25 Mounting position 3 ...

Страница 29: ...perating Instructions 02 2013 C98130 A7589 A1 3 7629 29 70 16 0 20 8 4 12 0 20 40 60 10 30 50 24 120 V 230 V 2XWSXW FXUUHQW 7HPSHUDWXUH r Figure 4 26 Mounting position 4 70 16 0 20 8 4 12 0 20 40 60 10 30 50 24 120 V 230 V 2XWSXW FXUUHQW 7HPSHUDWXUH r Figure 4 27 Mounting position 5 ...

Страница 30: ...0 0 0 20 40 60 10 30 50 120 V 230 V 4 5 2 1 3 6 7 8 2XWSXW FXUUHQW 7HPSHUDWXUH r Figure 4 28 Mounting position 1 SITOP PSU100S IN OUT 70 0 0 20 40 60 10 30 50 120 V 230 V 4 5 2 1 3 6 7 8 2XWSXW FXUUHQW 7HPSHUDWXUH r Figure 4 29 Mounting position 2 SITOP PSU100S IN OUT 70 0 0 20 40 60 10 30 50 120 V 230 V 4 5 2 1 3 6 7 8 2XWSXW FXUUHQW 7HPSHUDWXUH r Figure 4 30 Mounting position 3 ...

Страница 31: ...perating Instructions 02 2013 C98130 A7589 A1 3 7629 31 70 0 0 20 40 60 10 30 50 120 V 230 V 4 5 2 1 3 6 7 8 2XWSXW FXUUHQW 7HPSHUDWXUH r Figure 4 31 Mounting position 4 70 0 0 20 40 60 10 30 50 120 V 230 V 4 5 2 1 3 6 7 8 2XWSXW FXUUHQW 7HPSHUDWXUH r Figure 4 32 Mounting position 5 ...

Страница 32: ... V 230 V 8 10 4 2 6 12 14 16 SITOP PSU100S IN OUT 2XWSXW FXUUHQW 7HPSHUDWXUH r Figure 4 33 Mounting position 1 70 0 0 20 40 60 10 30 50 120 V 230 V 8 10 4 2 6 12 14 16 SITOP PSU100S IN OUT 2XWSXW FXUUHQW 7HPSHUDWXUH r Figure 4 34 Mounting position 2 70 0 0 20 40 60 10 30 50 120 V 230 V 8 10 4 2 6 12 14 16 SITOP PSU100S IN OUT 2XWSXW FXUUHQW 7HPSHUDWXUH r Figure 4 35 Mounting position 3 ...

Страница 33: ...ting Instructions 02 2013 C98130 A7589 A1 3 7629 33 70 0 0 20 40 60 10 30 50 120 V 230 V 8 10 4 2 6 12 14 16 2XWSXW FXUUHQW 7HPSHUDWXUH r Figure 4 36 Mounting position 4 70 0 0 20 40 60 10 30 50 120 V 230 V 8 10 4 2 6 12 14 16 2XWSXW FXUUHQW 7HPSHUDWXUH r Figure 4 37 Mounting position 5 ...

Страница 34: ...Mounting position mounting clearances 4 2 Other mounting positions SITOP PSU100S 34 Operating Instructions 02 2013 C98130 A7589 A1 3 7629 ...

Страница 35: ...TT system according to VDE 0100 T 300 IEC 364 3 with a rated voltage of 120 230 V AC 50 60 Hz Figure 5 1 Line connection examples 6EP1334 2BA20 and 6EP1336 2BA10 The line supply is connected using terminals L1 N and PE see Figure 5 1 Line connection examples 6EP1334 2BA20 and 6EP1336 2BA10 Page 35 and must be implemented according to IEC 60364 and EN 50178 A protective device miniature circuit bre...

Страница 36: ...6EP1334 2BA20 Miniature circuit breaker IEC 898 characteristic C 10 A 6EP1336 2BA10 Miniature circuit breaker IEC 898 characteristic C 10 A or circuit breaker 3RV2411 1JA10 120 V or 3RV2411 1FA10 230 V 6EP1322 2BA00 Miniature circuit breaker IEC 898 characteristic C 6 A 6EP1323 2BA00 Miniature circuit breaker IEC 898 characteristic C 10 A The protective conductor of the line supply must be connect...

Страница 37: ...EP1334 2BA20 and 6EP1336 2BA10 The output voltage is connected via the and terminals at the output of the power supply see Figure 5 2 Connecting the output voltage examples 6EP1334 2BA20 and 6EP1336 2BA10 Page 37 Ensure that the output cables are dimensioned correctly for the maximum output current rms value and fused accordingly Note If the safety concept of the plant or system specifies that the...

Страница 38: ...Installation 5 2 Output side connection SITOP PSU100S 38 Operating Instructions 02 2013 C98130 A7589 A1 3 7629 ...

Страница 39: ...eshold typical 80 V 61 V 77 V 63 V 70 V 66 V 80 V 78 V or 160 V 155 V Power failure buffering at Ia rated min 20 ms 20 ms 20 ms 20 ms Power failure buffering at 93 187 V at 120 230 V Rated line frequency 50 60 Hz Line frequency range 47 63 Hz Input current at rated value of input voltage 120 V 1 25 A 2 34 A 4 49 A 7 5 A Input current at rated value of input voltage 230 V 0 74 A 1 36 A 1 91 A 3 5 A...

Страница 40: ...Rated voltage Ue rated 120 230 V Voltage range 85 132 170 264 V automatic range switchover Yes Connect shutdown threshold typical 82 V 66 V 66 V 63 V Power failure buffering at Ia rated min 20 ms 20 ms Power failure buffering at 93 187 V Rated line frequency 50 60 Hz Line frequency range 47 63 Hz Input current at rated value of input voltage 120 V 1 73 A 3 24 A Input current at rated value of inpu...

Страница 41: ... 3 3 3 Static line regulation approx 0 1 0 1 0 1 0 5 Static load regulation approx 1 1 1 1 Residual ripple Peak peak max 150 mV 150 mV 150 mV 150 mV in the load range 100 mA 300 mV in the load range up to 100 mA Spikes peak peak max bandwidth 200 MHz 240 mV 240 mV 240 mV 240 mV Adjustment range 22 8 28 0 V 24 28 0 V Product function output voltage can be adjusted Yes Output voltage setting Remark ...

Страница 42: ...C derating 3 Ia rated K 0 20 A 24 A to 45 C 60 to 70 C derating 5 Ia rated K Output active power typical 60 W 120 W 240 W 480 W Overload capability Extra Power 3 75 A for 5 s min 7 5 A for 5 s min 15 A for 5 s min 30 A for 5 s min Short time overload current for a short circuit when powering up typical 9 A 18 A 33 A 35 A Duration of the overload capability overcurrent for a short circuit while pow...

Страница 43: ...dual ripple Peak peak max 150 mV 150 mV Spikes peak peak max bandwidth 200 MHz 240 mV 240 mV Adjustment range 11 5 15 5 V Product function output voltage can be adjusted Yes Output voltage setting Using a potentiometer Status display LED green for 12 V O K Signaling Relay contact NO contact rating 60 V DC 0 3 A for 12 V O K Response when switching on off Overshoot of Ua 360 mV Starting delay max 3...

Страница 44: ...Duration of the overload capability overcurrent for a short circuit in operation Remark 800 ms once only 800 ms once only Can be connected in parallel to increase the power rating Yes Number of devices that can be connected in parallel to increase the power rating units 2 Output characteristic see diagram output characteristic for 6EP1322 2BA20 Page 46 see diagram output characteristic for 6EP1323...

Страница 45: ...5 10 5 15 30 4 2XWSXW YROWDJH 9 2XWSXW FXUUHQW Figure 6 3 Output characteristic 6EP1332 2BA20 7 0 2 4 6 1 3 5 20 0 25 10 5 15 30 8 2XWSXW YROWDJH 9 2XWSXW FXUUHQW Figure 6 4 Output characteristic 6EP1333 2BA20 14 0 4 8 12 2 6 10 20 0 25 10 5 15 30 16 2XWSXW YROWDJH 9 2XWSXW FXUUHQW Figure 6 5 Output characteristic 6EP1334 2BA20 ...

Страница 46: ...racteristic 6EP1336 2BA10 7 0 2 4 6 1 3 5 10 0 12 4 2 6 14 10 8 9 8 2XWSXW YROWDJH 9 2XWSXW FXUUHQW Figure 6 7 Output characteristic 6EP1322 2BA00 14 0 4 8 12 2 6 10 10 0 12 4 2 6 14 18 8 16 2XWSXW YROWDJH 9 2XWSXW FXUUHQW Figure 6 8 Output characteristic 6EP1323 2BA00 The device supplies a constant output voltage until the current limit is reached In the event of an overload the output current an...

Страница 47: ...6 87 89 90 89 90 Power loss at Ua rated Ia rated 120 V 230 V AC approx 11 W 10 W 18 W 16 W 27 W 25 W 59 W 53 W Power loss when idling 120 V 230 V AC approx 1 7 W 1 2 W 1 8 W 1 3 W 3 0 W 2 4 W 4 1 W 3 6 W 6EP1322 2BA00 6EP1323 2BA00 Efficiency at Ua rated Ia rated 120 V 230 V AC approx 82 83 86 87 Power loss at Ua rated Ia rated 120 V 230 V AC approx 16 W 15 W 27 W 15 W Power loss when idling 120 V...

Страница 48: ...5 A 2 5 A 3 75 A 80 80 100 120 140 160 180 84 85 82 81 83 86 87 88 200 89 90 220 240 260 280 IILFLHQF QSXW YROWDJH 9 Figure 6 10 Efficiency 6EP1333 2BA20 7 5 A 5 A 10 A 5 A 10 A 7 5 A 85 80 100 120 140 160 180 89 90 87 86 88 91 92 93 200 94 95 220 240 260 280 IILFLHQF QSXW YROWDJH 9 Figure 6 11 Efficiency 6EP1334 2BA20 ...

Страница 49: ... A 10 A 20 A 85 80 100 120 140 160 180 89 90 87 86 88 91 92 93 200 94 95 220 240 260 280 IILFLHQF QSXW YROWDJH 9 Figure 6 12 Efficiency 6EP1336 2BA10 5 25 A 3 5 A 7 A 7 A 3 5 A 5 25 A 80 80 100 120 140 160 180 84 85 82 81 83 86 87 88 200 89 90 220 240 260 280 IILFLHQF QSXW YROWDJH 9 Figure 6 13 Efficiency 6EP1322 2BA00 ...

Страница 50: ...iciency 6EP1323 2BA00 6 4 Closed loop control 6EP1332 2BA20 6EP1333 2BA20 6EP1334 2BA20 6EP1336 2BA10 6EP1322 2BA00 6EP1323 2BA00 Dyn line regulation Ue rated 15 max 3 UA 3 UA 3 UA Dyn load regulation Ia 10 90 10 max 5 UA 15 UA Dyn load regulation Ia 10 90 10 typ 3 UA Load step settling time 10 to 90 max 1 ms 10 ms 1 ms Load step settling time 10 to 90 typ 2 ms Load step settling time 90 to 10 max...

Страница 51: ...tatically limited Electronic trip automatic restart hiccup Continuous short circuit current rms value approx 3 4 A 7 3 A 14 6 A 7 A Overload short circuit display 6EP1322 2BA00 6EP1323 2BA00 Output overvoltage protection Yes according to EN 60950 Current limitation typ Remark 10 5 A Overload capability with 150 Ia rated up to 5 s min 21 A Overload capability with 150 Ia rated up to 5 s min Short c...

Страница 52: ...h for 0 2 4 mm Connections auxiliary contacts Signals 2 screw terminals for 0 5 mm 2 5 mm 13 14 signal 1 screw terminal each for 0 14 1 5 mm Width of the housing 32 5 mm 50 mm 70 mm 115 mm Height of the housing 125 mm 125 mm 125 mm 145 mm Depth of the housing 120 mm 120 mm 120 mm 150 mm Installation width 32 5 mm 50 mm 70 mm 120 mm Mounting height 225 mm 225 mm 225 mm 245 mm Weight approx 0 32 kg ...

Страница 53: ...ddb index aspx objKey G_KT01_XX_00727 6EP1333 2BA20 http www automation siemens com bilddb index aspx objKey G_KT01_XX_00730 6EP1334 2BA20 http www automation siemens com bilddb index aspx objKey G_KT01_XX_00733 6EP1336 2BA10 http www automation siemens com bilddb index aspx objKey G_KT01_XX_00720 6EP1322 2BA00 http www automation siemens com bilddb index aspx objKey G_KT01_XX_00736 6EP1323 2BA00 ...

Страница 54: ...Technical data 6 8 Dimension drawing SITOP PSU100S 54 Operating Instructions 02 2013 C98130 A7589 A1 3 7629 ...

Страница 55: ...6 2BA10 6EP1322 2BA00 6EP1323 2BA00 Primary secondary galvanic isolation Yes Galvanic isolation SELV output voltage Ua according to EN 60950 1 and EN 50178 Transformer according to EN 61558 2 16 Protection class Class I Degree of protection EN 60529 IP20 Leakage current typ 1 mA Leakage current max 3 5 mA Test voltage See Table 7 1 Test voltage Page 56 ...

Страница 56: ...minals with one another L N Connect the output terminals signaling contact and PE with one another Test C Connect the output terminals and signaling contact with one another and measure with respect to PE Table 7 1 Test voltage Test time Prim sec A Prim PE B Sec PE C 60 s 4200 VDC 2200 VDC 700 VDC Type test 60 s 3000 VAC 1500 VAC 500 VAC 1 s 2200 VDC 2200 VDC 500 VDC Production test 1 s 1500 VAC 1...

Страница 57: ...ing Yes 2004 108 EG and 2006 95 EG CSA approval Yes CSA C22 2 No 60950 1 cCSAus ANSI ISA 12 12 01 UL cUL approval cULus listed UL 508 CSA 22 2 No 107 1 File E197259 Explosion protection ATEX EX II 3G Ex nA nC IIC T4 Gc cCSAus Class I Div 2 GROUPS A B C D T4 CB approval Yes CB Scheme IEC 60950 1 SEMI F47 compliance Not tested fulfilled Marine approvals Germanischer Lloyd GL available soon Germanisc...

Страница 58: ... at DC output 4 kV at line connections 2 kV at DC output Surge voltages EN 61000 4 5 2 kV symmetrical at the line connections 4 kV symmetrical at the line connections 500 V symmetrical asymmetrical on DC output cables High frequency fields EN 61000 4 6 10 V 0 15 80 MHz 10 V 0 15 80 MHz Magnetic fields EN 61000 4 8 Not applicable 30 A m 50 Hz Voltage dips EN 61000 4 11 100 for 20 ms 60 for 200 ms 3...

Страница 59: ...or 12 V versions from 55 C 5 Ia rated K 0 70 C with natural convection self convection Derating from 60 C 5 Ia rated K from Ue 100 V or Ue 200 V and lower output power is reduced depending on the ambient temperature 100 0 20 0 100 200 300 50 150 250 40 60 80 120 45 C 60 C 3RZHU FKDQJH QSXW YROWDJH 9DF Ambient temperature Tested according to EN 60068 2 1 cold EN 60068 2 2 dry heat EN 60068 2 78 hum...

Страница 60: ... 60068 2 27 shock test Ea acceleration 150 m s2 test duration 11 ms Damaging gases Tested according to EN 60068 2 42 sulfur dioxide EN 60068 2 43 hydrogen sulfide Atmospheric pressure Operation 1080 795 hPa 1000 2000 m For operation at altitudes of 2000 m up to 6000 m above sea level output must be derated by 7 5 1000 m or the ambient temperature must be reduced by 5 K 1000 m see Figure 4 7 Mounti...

Страница 61: ...r cable e g with the main switch available in control cabinets The output voltages measured in no load operation for the power supplies that are not yet connected in parallel should not deviate more than a maximum of 50 mV This usually corresponds to the factory setting If the output voltage is changed you should connect the terminals and then in no load operation measure the voltage difference be...

Страница 62: ...redundancy module two 24 V power supplies of the same type up to 20 A can be decoupled Figure 9 2 Redundant configuration with two power supplies and SITOP PSE202U redundancy module Page 62 When one of the devices fails then the other automatically takes over the power supply If one of the power supplies fails then this is signaled using an LED on the redundancy module as well as an isolated relay...

Страница 63: ...wer supply The terminal of the first power supply and the terminal of the second power supply are routed to the load Depending on the grounding point of the secondary output voltages voltages of 48 V 24 V or 48 V can be realized In the case of an asymmetric load distribution it is not possible to guarantee correct functionality WARNING SELV is not guaranteed in the case of a fault When connecting ...

Страница 64: ...s with adjustable output current range for each channel from 0 5 3 A and 3 10 A is available this monitors the 24 V branches for overloading and short circuiting Figure 9 4 Electronic protection of 24 V loads using the SITOP PSE200U selectivity module Page 64 Brief current peaks e g as a result of a high inrush current are permitted and branches with a longer overload are switched into a no curren...

Страница 65: ...ne buffering time in the device using an additional SITOP PSE201M buffer module The SITOP PSE201M buffer module based on electrolytic capacitors is connected in parallel to the 24 V power supply output Figure 9 5 Buffering brief power failures using the SITOP PSE201M buffer module Page 65 The buffer time is 200 ms at 40 A up to 1 6 s for a load current of 5 A This time can be increased a multiple ...

Страница 66: ...ortfolio includes various DC UPS solutions to prevent the failure of the 24 V power supply voltage Power supply failures up into the minutes range can be buffered using the maintenance free SITOP UPS500 DC UPS modules based on capacitors Figure 9 6 24 V buffering to allow the saving of process data and controlled shutdown of PCs Page 66 3RZHU VXSSO 9 EXIIHUHG QGXVWULDO 3 9 XQEXIIHUHG FWXDWRUV H J ...

Страница 67: ...HPHQWDO HQFRGHU 6 723 836 DWWHU PRGXOH 3 6ZLWFK Figure 9 7 24 V buffering to maintain communication signaling functions sensor measured values and position values Using the free of charge SITOP DC UPS software tool DC UPS systems can be simply integrated into PC based automation solutions This supports further processing of the status signals and safely running down the PC You can find additional ...

Страница 68: ...Applications 9 6 Protecting against longer power failures SITOP PSU100S 68 Operating Instructions 02 2013 C98130 A7589 A1 3 7629 ...

Страница 69: ...7629 69 Environment 10 The device is in conformance with RoHS As a rule only non silicon precipitating materials are used Disposal guidelines Packaging and packaging aids can and should always be recycled The product itself may not be disposed of as domestic refuse ...

Страница 70: ...Environment SITOP PSU100S 70 Operating Instructions 02 2013 C98130 A7589 A1 3 7629 ...

Страница 71: ...r supplies is available in the Internet at the SITOP homepage SITOP http www siemens de sitop Information material SITOP information can be downloaded from the Internet Information and download center http www siemens de sitop infomaterial CAx data 2D 3D data and circuit diagram macros can be downloaded from the Internet Siemens image database http www siemens de sitop cax Request all CAx data via...

Страница 72: ...9 A1 3 7629 Contact persons If you have any questions regarding the use of our products then contact the Siemens contact person in your regional Siemens sales office You can find these addresses as follows On the Internet http www siemens de automation partner In Catalog CA 01 ...

Отзывы: