Technical data
6.2 Output
SITOP PSU100S
42
Operating Instructions, 02.2013, C98130-A7589-A1-3-7629
6EP1332-2BA20
6EP1333-2BA20
6EP1334-2BA20
6EP1336-2BA10
Response when
switching on/off
Overshoot of Ua<720 mV
No overshoot of Ua
(soft start), with the
exception of a
capacitive load
Starting delay, max.
300 ms
300 ms
300 ms
1.5 s
Start delay, typ.
200 ms
160 ms
150 ms
500 ms
Voltage rise
120 V / 230 V AC max.
100 ms
100 ms
100 ms
500 ms
Voltage rise
120 V / 230 V AC typ.
15 ms
15 ms
20 ms
50 ms
Rated current Ia rated 2.5 A
5 A
10 A
20 A
Current range
Remark
0...2.5 A
3 A to +45° C
+60 to +70 °C;
derating: 3 % Ia
rated/K
0...5 A
6 A to +45° C
+60 to +70 °C;
derating: 3 % Ia
rated/K
0...10 A
12 A to +45° C
+60 to +70 °C;
derating: 3 % Ia
rated/K
0...20 A
24 A to +45° C
+60 to +70 °C;
derating: 5 % Ia
rated/K
Output active power /
typical
60 W
120 W
240 W
480 W
Overload capability
(Extra Power)
3.75 A for 5 s/min
7.5 A for 5 s/min
15 A for 5 s/min
30 A for 5 s/min
Short-time overload
current / for a short
circuit when powering
up / typical
9 A
18 A
33 A
35 A
Duration of the
overload capability,
overcurrent / for a
short circuit while
powering up
Remark
800 ms
once-only
800 ms
once-only
800 ms
once-only
100 ms
every 2.5 s
Short-time overload
current / for a short
circuit in operation /
typical
9 A
18 A
33 A
35 A
Duration of the
overload capability,
overcurrent / for a
short circuit in
operation
Remark
800 ms
once-only
800 ms
once-only
800 ms
once-only
100 ms
every 2.5 s
Can be connected in
parallel to increase the
power rating
Yes
Number of devices
that can be connected
in parallel to increase
the power rating, units
2
Содержание SITOP PSU100S
Страница 8: ...Safety instructions SITOP PSU100S 8 Operating Instructions 02 2013 C98130 A7589 A1 3 7629 ...
Страница 38: ...Installation 5 2 Output side connection SITOP PSU100S 38 Operating Instructions 02 2013 C98130 A7589 A1 3 7629 ...
Страница 54: ...Technical data 6 8 Dimension drawing SITOP PSU100S 54 Operating Instructions 02 2013 C98130 A7589 A1 3 7629 ...
Страница 70: ...Environment SITOP PSU100S 70 Operating Instructions 02 2013 C98130 A7589 A1 3 7629 ...