Technical data
6.5 Protection and monitoring
SITOP PSU100S
Operating Instructions, 02.2013, C98130-A7589-A1-3-7629
51
6.5
Protection and monitoring
6EP1332-2BA20
6EP1333-2BA20
6EP1334-2BA20
6EP1336-2BA10
Output overvoltage
protection
Yes, according to EN 60950
Current limitation
Typ.
Remark
3.75 A
Overload capability
with
150 % Ia rated up to
5 s/min
7.5 A
Overload capability
with
150 % Ia rated up to
5 s/min
15 A
Overload capability
with
150 % Ia rated up to
5 s/min
21.5 A (>45 °C)
25.5 A (<45 °C)
Overload capability
with
150 % Ia rated up to
5 s/min
Short-circuit protection Yes, current is statically limited
Electronic trip,
automatic restart
(hiccup)
Continuous short-
circuit current rms
value, approx.
3.4 A
7.3 A
14.6 A
7 A
Overload / short-circuit
display
-
6EP1322-2BA00
6EP1323-2BA00
Output overvoltage protection
Yes, according to EN 60950
Current limitation, typ.
Remark
10.5 A
Overload capability with
150 % Ia rated up to 5 s/min
21 A
Overload capability with
150 % Ia rated up to 5 s/min
Short-circuit protection
Yes, current is statically limited
Continuous short-circuit current
rms value, approx.
8.8 A
16.4 A
Overload / short-circuit display
-
6.6
MTBF
6EP1332-2BA20
6EP1333-2BA20
6EP1334-2BA20
6EP1322-2BA00
6EP1323-2BA00
6EP1336-2BA10
Mean Time Between Failures
SN29500:
> 1600000 h
at 40 °C, rated load, 24 h operation
SN29500:
>500000 h (typ. 700000 h)
at 40° C, rated load, 24 h operation
Содержание SITOP PSU100S
Страница 8: ...Safety instructions SITOP PSU100S 8 Operating Instructions 02 2013 C98130 A7589 A1 3 7629 ...
Страница 38: ...Installation 5 2 Output side connection SITOP PSU100S 38 Operating Instructions 02 2013 C98130 A7589 A1 3 7629 ...
Страница 54: ...Technical data 6 8 Dimension drawing SITOP PSU100S 54 Operating Instructions 02 2013 C98130 A7589 A1 3 7629 ...
Страница 70: ...Environment SITOP PSU100S 70 Operating Instructions 02 2013 C98130 A7589 A1 3 7629 ...