Ambient conditions
SITOP PSU100S
60
Operating Instructions, 02.2013, C98130-A7589-A1-3-7629
6EP1332-2BA20
6EP1333-2BA20
6EP1334-2BA20
6EP1322-2BA00
6EP1323-2BA00
6EP1336-2BA10
Mechanical stressing in operation
Tested according to:
EN 60068-2-6 vibration, test Fc:
3.5 mm deflection in the range 5 – 8.4 Hz
2 g acceleration in the range 8.4 – 150 Hz
EN 60068-2-27 shock, test Ea:
acceleration 150 m/s
2
, test duration 11 ms
Damaging gases
Tested according to:
EN 60068-2-42 sulfur dioxide
EN 60068-2-43 hydrogen sulfide
Atmospheric pressure
Operation:
1080 ... 795 hPa (-1000 ... +2000 m)
For operation at altitudes of 2000 m up to 6000 m above sea level:
output must be derated by -7.5 % / 1000 m or
the ambient temperature must be reduced by 5 K / 1000 m
see Figure 4-7 Mounting height derating (Page 21)
Overvoltage category:
III up to 2000 m (EN 50178)
II from 2000 m up to 6000 m (EN 50178)
Storage:
1080 ... 660 hPa (-1000 ... +3500 m)