Technical data
6.1 Input
SITOP PSU100S
40
Operating Instructions, 02.2013, C98130-A7589-A1-3-7629
6EP1332-2BA20
6EP1333-2BA20
6EP1334-2BA20
6EP1336-2BA10
Protection in the line
feeder cable (IEC 898)
required: Circuit
breaker, C
characteristic, 3 A
required: Circuit
breaker, C
characteristic, 6 A
required: Circuit
breaker, C
characteristic, 10 A
required: Circuit
breaker, C
characteristic, 10 A
or
Circuit breaker
3RV2411-1JA10
(120 V) or 3RV2411-
1FA10 (230 V)
Overvoltage strength -
-
-
2.3 × Ue rated, 1.3 ms
6EP1322-2BA00
6EP1323-2BA00
Input
1-phase, AC
Rated voltage Ue rated
120 / 230 V
Voltage range
85-132 / 170-264 V
automatic range switchover
Yes
Connect/shutdown threshold,
typical
82 V / 66 V
66 V / 63 V
Power failure buffering at
Ia rated, min
20 ms
20 ms
Power-failure buffering
at 93 / 187 V
Rated line frequency
50/60 Hz
Line frequency range
47...63 Hz
Input current / at rated value of
input voltage 120 V
1.73 A
3.24 A
Input current / at rated value of
input voltage 230 V
0.99 A
1.41 A
Switch-on current limitation
(+25 °C), max.
45 A
60 A
I²t, at 120 V AC, max.
0.3 A
2
s
1.6 A
2
s
I²t, at 230 V AC, max.
1.0 A
2
s
5.6 A
2s
Integrated input fuse
Fuse T 3,15 A
Fuse T 6 A
Protection in the line feeder
cable (IEC 898)
required: Circuit breaker, C
characteristic, 3 A
required: Circuit breaker, C
characteristic, 6 A
Содержание SITOP PSU100S
Страница 8: ...Safety instructions SITOP PSU100S 8 Operating Instructions 02 2013 C98130 A7589 A1 3 7629 ...
Страница 38: ...Installation 5 2 Output side connection SITOP PSU100S 38 Operating Instructions 02 2013 C98130 A7589 A1 3 7629 ...
Страница 54: ...Technical data 6 8 Dimension drawing SITOP PSU100S 54 Operating Instructions 02 2013 C98130 A7589 A1 3 7629 ...
Страница 70: ...Environment SITOP PSU100S 70 Operating Instructions 02 2013 C98130 A7589 A1 3 7629 ...