Technical data
6.3 Efficiency
SITOP PSU100S
Operating Instructions, 02.2013, C98130-A7589-A1-3-7629
47
When the output voltage falls below approx. 10 V, the 6EP1336-2BA10 device switches off,
and automatically restarts. This response is repeated as long as the overload condition is
present.
6.3
Efficiency
6EP1332-2BA20
6EP1333-2BA20
6EP1334-2BA20
6EP1336-2BA10
Efficiency at Ua rated, Ia rated
120 V / 230 V AC approx.
83 % / 85 %
86 % / 87 %
89 % / 90 %
89 % / 90 %
Power loss at Ua rated, Ia rated
120 V / 230 V AC approx.
11 W / 10 W
18 W / 16 W
27 W / 25 W
59 W / 53 W
Power loss when idling
120 V / 230 V AC approx.
1.7 W / 1.2 W
1.8 W / 1.3 W
3.0 W / 2.4 W
4.1 W / 3.6 W
6EP1322-2BA00
6EP1323-2BA00
Efficiency at Ua rated, Ia rated
120 V / 230 V AC approx.
82 % / 83 %
86 % / 87 %
Power loss at Ua rated, Ia rated
120 V / 230 V AC approx.
16 W / 15 W
27 W / 15 W
Power loss when idling
120 V / 230 V AC approx.
1.5 W / 1.0 W
2.8 W / 2.3 W
1,875 A
1,25 A
2,5 A
2,5 A
1,25 A
1,875 A
80
80
100
120
140
160
180
84
85
82
81
83
86
87
88
200
89
90
220
240
260
280
(I
IL
F
LH
Q
F\
>
@
,QSXWYROWDJH>9@
Figure 6-9
Efficiency 6EP1332-2BA20
Содержание SITOP PSU100S
Страница 8: ...Safety instructions SITOP PSU100S 8 Operating Instructions 02 2013 C98130 A7589 A1 3 7629 ...
Страница 38: ...Installation 5 2 Output side connection SITOP PSU100S 38 Operating Instructions 02 2013 C98130 A7589 A1 3 7629 ...
Страница 54: ...Technical data 6 8 Dimension drawing SITOP PSU100S 54 Operating Instructions 02 2013 C98130 A7589 A1 3 7629 ...
Страница 70: ...Environment SITOP PSU100S 70 Operating Instructions 02 2013 C98130 A7589 A1 3 7629 ...