SITOP PSU100S
Operating Instructions, 02.2013, C98130-A7589-A1-3-7629
39
Technical data
6
Note
Technical data is applicable for a rated input voltage, rated load and +25° C ambient
temperature (if nothing else is specified).
6.1
Input
6EP1332-2BA20
6EP1333-2BA20
6EP1334-2BA20
6EP1336-2BA10
Input
1-phase, AC
Rated voltage
Ue rated
120 / 230 V
Voltage range
85-132 / 170-264 V
85-132 / 176-264 V
automatic range
switchover
Yes
Connect/shutdown
threshold, typical
80 V / 61 V
77 V / 63 V
70 V / 66 V
80 V/78 V or
160 V/155 V
Power failure buffering
at Ia rated, min
20 ms
20 ms
20 ms
20 ms
Power-failure buffering at 93 / 187 V
at 120 / 230 V
Rated line frequency
50/60 Hz
Line frequency range
47...63 Hz
Input current / at rated
value of input voltage
120 V
1.25 A
2.34 A
4.49 A
7.5 A
Input current / at rated
value of input voltage
230 V
0.74 A
1.36 A
1.91 A
3.5 A
Switch-on current
limitation (+25 °C),
max.
33 A
40 A
60 A
11 A
I²t, at 120 V AC, max
0.1 A
2
s
0.3 A
2
s
1.6 A
2
s
2.5 A
2
s
I²t, at 230 V AC, max. 0.4 A
2
s
1.0 A
2
s
5.6 A
2
s
10 A
2
s
Integrated input fuse
Fuse T 3.15 A
Fuse T 3.15 A
Fuse T 6 A
Fuse T 10 A
Содержание SITOP PSU100S
Страница 8: ...Safety instructions SITOP PSU100S 8 Operating Instructions 02 2013 C98130 A7589 A1 3 7629 ...
Страница 38: ...Installation 5 2 Output side connection SITOP PSU100S 38 Operating Instructions 02 2013 C98130 A7589 A1 3 7629 ...
Страница 54: ...Technical data 6 8 Dimension drawing SITOP PSU100S 54 Operating Instructions 02 2013 C98130 A7589 A1 3 7629 ...
Страница 70: ...Environment SITOP PSU100S 70 Operating Instructions 02 2013 C98130 A7589 A1 3 7629 ...