3RV1 circuit breakers
SIRIUS System Manual
GWA 4NEB 430 0999-02b
2-19
Table 2-5: Attachable accessories
2.4.2 Auxiliary switch, alarm switch, and auxiliary release
The maximum configuration for each 3RV1 circuit breaker is one transverse
auxiliary switch, one lateral auxiliary switch, one alarm switch, and one aux-
iliary release.
Possible combinations
The following combinations of auxiliary switches and alarm switches or of
auxiliary switches are possible:
• Auxiliary and alarm switches can be installed individually or together. The
lateral auxiliary switch is installed on the left of the alarm switch.
• Transverse and lateral auxiliary switches can be combined.
• One auxiliary release can be attached on the right for each circuit breaker:
Mounting the
auxiliary switches
The auxiliary switches, alarm switches, and auxiliary releases are mounted
in the same way for all frame sizes:
Transverse auxiliary switch (3RV1901-1D, -1E, -1F)
Figure 2-10: Mounting the transverse auxiliary switch (frame size S00)
Accessories
Function/use
Width
Attach to
Disconnecting
module
Frame sizes
S0 and S2
The supply is fed to the circuit breaker via the disconnecting module.
A connector which can only be removed when the circuit breaker is
switched off isolates the circuit breaker from the power system on 3
poles.
The shock-protected isolation position is easily visible and is secured
by a padlock to ensure that the connector cannot be used during
maintenance work, for example.
Width of
the cir-
cuit
breaker
remains
the same
Upper side
Motorized
remote-control
mechanism
For frame sizes
S2 and S3
The circuit breakers can be opened and closed via the remote-con-
trolled mechanism by means of electrical commands. This enables a
load or system to be disconnected from and then reconnected to the
power system from an operator control panel.
The circuit breaker can be disconnected from and reconnected to the
remote-control mechanism in situ.
Rotary switch
extension for
the door
The rotary switch extension for the door consists of a knob, a drive
coupling and an extension shaft. They comply with IP 65. The door
interlock prevents the cubicle door being opened inadvertently when
the switch is in the on position. The off position can be secured with
a maximum of 3 padlocks.
Emergency stop
rotary switch
extension
Rotary switch extension with emergency stop function.
1
2
3RV 1901-1D, -1E