7.1 Specifications/regulations/approvals
Standards
The time relays comply with the following standards:
• IEC 61812-1/DIN VDE 0435 Part 2021 on electrical relays and time relays
• IEC 61000 on electromagnetic compatibility
• IEC 60947-5-1; DIN VDE 0660 Part 200 on low-voltage switchgear
• IEC 60721-3-1/-3 on environmental conditions
• IEC 60529 on degree of protection
Electromagnetic com-
patibility
The time relays are tested in acc. with EN 50 081-1 (emission) and
EN 50 082-2 (immunity) and are thus noise-free and surge-proof.
Switching capacity
The switching capacity complies with IEC 60947-5-1
• In the case of utilization category AC-15 and 230 VAC: 3 A
• In the case of utilization category DC-13 and 24 VDC: 1 A
• In the case of utilization category DC-13 and 48 VDC: 0.45 A
• In the case of utilization category DC-13 and 60 VDC: 0.35 A
• In the case of utilization category DC-13 and 110 VDC: 0.2 A
• In the case of utilization category DC-13 and 230 VDC: 0.1 A
UL/CSA/marine
approval
The SIMIREL time relays are approved by UL and CSA for use worldwide
and tested by the GL, LRS, DM marine authorities.
Approvals/
test reports
Confirmation of approvals, test certificates, and the declaration of confor-
mity can be obtained on the Internet/intranet.