3RV1 circuit breaker
SIRIUS System Manual
2-58
GWA 4NEB 430 0999-02b
2.7 Technical specifications
2.7.1 General specifications
Type
3RV1. 1
3RV1. 2
3RV1. 3
3RV1. 4
Specifications
• IEC 60 947-1, EN 60 947-1 (VDE 0660 Part 100)
Yes
• IEC 60 947-2, EN 60 947-2 (VDE 0660 Part 101)
Yes
• IEC 60 947-4-1, EN 60 947-4-1 (VDE 0660 Part 102)
Yes
Frame size
S00
S0
S2
S3
Pole number
3
Max. rated current
I
nmax
(= max. rated operational current
I
e
)
A
12
25
50
100
Permissible ambient temperature
Storage/transportation
°C
-50 to +80
Operation
°C
-20 to +70
1
)
Permissible rated current with the following internal cubicle temperature:
• +60 °C
%
100
• +70 °C
%
87
Circuit breaker in housing
Permissible rated current with the following ambient housing temperature:
• +35 °C
%
100
• +60 °C
%
87
Rated operational voltage U
e
V
690
2
)
Rated frequency
Hz
50/60
Rated insulation voltage U
i
V
690
Rated impulse strength
U
imp
kV
6
Utilization category
• IEC 60 947-2 (circuit breaker)
A
• IEC 60 947-4-1 (motor starter)
AC-3
CLASS
In acc. with IEC 60 947-4-1
10
10/20
Direct current short-circuit breaking capacity
(time constant
τ
= 5 ms)
(time constant t = 5 ms)
• 1 conducting path 150 VDC
kA
10
• 2 conducting paths in series 300 VDC
kA
10
• 3 conducting paths in series 450 VDC
kA
10
Power loss (Pv) per circuit breaker
I
n
-> to 1.25 A
W
5
-
-
-
Depends on rated current
I
n
I
n
-> 1.6 A to 6.3 A
W
6
-
-
-
(Upper setting range)
I
n
-> 8 A to 12 A
W
7
-
-
-
I
n
-> to 0.63 A
W
-
5
-
-
R
per conducting path
= P/
I
2
× 3
I
n
-> 0.8 A to 6.3 A
W
-
6
-
-
I
n
-> 8 A to 16 A
W
-
7
-
-
I
n
-> 20 A to 25 A
W
-
8
-
-
I
n
-> to 25 A
W
-
-
12
-
I
n
-> 32 A
W
-
-
15
-
I
n
-> 40 A to 50 A
W
-
-
20
-
I
n
-> to 63 A
W
-
-
-
20
I
n
-> 75 A and 90 A
W
-
-
-
30
I
n
-> to 100 A
W
-
-
-
38