3RV1 circuit breaker
SIRIUS System Manual
2-62
GWA 4NEB 430 0999-02b
Permissible rating of approved devices for North America,
u s
3RV10.A circuit breaker as "Combination Motor Controller Type E"
Since 16.07.2001, 1 inch air clearance and 2 inch creepage distance is required for a "Combination Motor Controller Type E" on the input
side with UL 508 The 3RV10 circuit breaker in frame sizes S0 and S3 are therefore approved with the terminal blocks listed below in
acc. with UL 508.
The 3RV10 circuit breaker in frame size S2 already complies with the required air clearance and creepage distance as a basic unit.
These extended air clearances and creepage distances are not required for CSA. The terminal blocks are therefore not required for use
as a "Combination Motor Controller Type E" in acc. with CSA. 3RV10 circuit breakers are certified as "Combination Motor Controller
Type E
" under the following file numbers with the listed data:
u
File No. E156943, Product Class NKJH
s
File No. LR12730, Product Class 3211 08
Hp rating = output power in horse power (maximum motor power)
FLA = full load amps
1) Corresponds to "short circuit breaking capacity" in acc. with UL
Circuit breaker
Hp rating
Rated current
To 240 VAC
To AC 480 Y/277 V
To AC 600 Y/347 V
For FLA max.
I
n
I
cu
1
)
I
cu
1
)
I
cu
1
)
Type
V
1-phase
3-phase
A
kA
kA
kA
0.11 to 1.6
50
50
30
3RV10 21
2
50
50
30
+ 3RV19 28-1H
115
2
-
2.5
50
50
30
200
3
7½
3.2
50
50
30
Frame size S0
230
3
7½
4
50
50
30
460
-
15
5
50
50
30
FLA max. 22 A, 480 V
575/600
-
10
6.3
50
50
30
12.5 A, 600 V
8
50
50
30
NEMA Size 1
10
50
50
30
12.5
50
50
30
16
50
50
-
20
50
50
-
22
50
50
-
0.9 to 16
50
50
25
3RV10 31
20
50
50
25
115
3
-
25
50
50
25
Frame size S2
200
7½
15
32
50
50
25
230
10
20
40
50
50
25
FLA max. 50 A, 600 V
460
-
40
45
50
50
25
NEMA Size 1
575/600
-
50
50
50
50
30
3RV10 31/3RV11 31
11 to 16
50
50
25
3RV13 31
20
50
50
25
115
3
-
25
50
50
25
Frame size S2
200
7½
15
32
50
50
25
230
10
20
40
50
50
25
FLA max. 50 A, 600 V
460
-
40
45
50
50
25
575/600
-
50
50
50
50
25
NEMA Size 2
11 to 16
50
50
30
3RV10 41
20
50
50
30
+ 3RT19 46-4GA07
115
10
-
25
50
50
30
200
20
30
32
50
50
30
Frame size S3
230
20
40
40
50
50
30
460
-
75
50
50
50
30
FLA max. 100 A, 480 V
575/600
-
75
63
50
50
30
75 A, 600 V
75
50
50
30
90
50
50
-
NEMA Size 3
100
50
50
-
Rating of the control switches and alarm switches
Lateral
auxiliary switch with
1 NO + 1 NC, 2 NO,
2 NC, 2 NO + 2 NC
and alarm switch
Transverse
auxiliary switch with
1 changeover contact
Transverse
auxiliary switch with
1 NO + 1 NC, 2 NO
Max. rated voltage
• In acc. with NEMA
u
VAC
600
240
• In acc. with NEMA
s
VAC
600
240
Continuous current
A
10
5
2.5
Switching capacity
A600
B600
C300
Q300
R300
R300