3RV1 circuit breaker
SIRIUS System Manual
2-60
GWA 4NEB 430 0999-02b
Conductor cross-sections - main circuit
Control switch
1) After the box terminals have been removed, lug or busbar connections are possible.
2) For notes on the Cage Clamp system, see pages 1-19.
3) Use an insulation stop for a conductor cross-section
≤
1 mm
2
.
5) Associated opening tool 8WA28 03/8WA28 04
Type
3RV1.
3RV1. 2
3RV1. 3
3RV1. 4
Connection type
Screw-type terminal
Screw-type terminal with box termi-
nal
Terminal screw
Pozidriv size 2
Pozidriv size 2
Allen screw 4 mm
Specified tightening torque
Nm
0.8 to 1.2 Nm
2 to 2.5
3 to 4.5
4 to 6
Conductor cross-sections, 1 or 2 conductors
Single-core
mm²
2 x (0.5 to 1.5)
2 x (1 to 2.5)
2 x (0.75 to 16)
2 x (2.5 to 16)
mm²
2 x (0.75 to 2.5)
(max. 4)
2 x (2.5 to 6)
-
-
Finely stranded with wire end ferrule:
mm²
2 x (0.5 to 1.5)
2 x (1 to 2.5)
2 x (0.75 to 16)
2 x (2.5 to 35)
mm²
2 x (0.75 to 2.5)
2 x (2.5 to 6)
(max. 10)
1 x (0.75 to 25)
1 x (2.5 to 50)
Stranded
mm²
2 x (0.5 to 1.5)
2 x (1 to 2.5)
2 x (0.75 to 25)
2 x (10 to 50)
mm²
2 x (0.75 to 2.5)
(max. 4)
2 x (2.5 to 6)
(max. 10)
1 x (0.75 to 35)
1 x (10 to 70)
AWG cables, single- or multi-core
AWG
2 x (18 to 14)
2 x (14 to 10)
2 x (18 to 3)
2 x (10 to 1/0)
AWG
-
-
1 x (18 to 2)
1 x (10 to 2/0)
Ribbon cables (number x width x depth)
mm
-
-
2 x (6 x 9 x 0.8)
2 x (6 x 9 x 0.8)
Removable box terminal
1
)
With copper busbars
mm
-
-
-
18 x 10
With lug
mm²
-
-
-
To 2 x 70
Cage Clamp connections
2
)
3
)
4
)
(1 or 2 conn. can be connected)
Single-coil
Finely stranded with wire end ferrule
Finely stranded without wire end ferrule
AWG cables, single-core or stranded
mm²
mm²
mm²
AWG
2 x (0.25 to 2.5)
2 x (0.25 to 1.5)
2 x (0.25 to 2.5)
2 x (24 to 14)
-
-
-
-
Max. outer diameter of the conductor insulation: 3.6 mm
Permissible service position
Any
In acc. with IEC 60 447 start com-
mand "I"
Right or above
Transverse auxiliary switch at front with 1 changeover contact
Switching capacity with different voltages
Rated operational voltage
U
e
AC voltage
VAC
24
230
400
690
Rated operational current
I
e
/AC-15
A
4
3
1.5
0.5
Rated operational current
I
e
/AC-12
I
th
A
10
10
10
10
Rated operational voltage
U
e
DC voltage
L/R
200 ms
VDC
24
110
220
Rated operational current
I
e
/DC-13
A
1
0.22
0.1
Transverse electronically optimized auxiliary switch at front with 1 changeover contact
Rated operational voltage
U
e
AC voltage
VAC
3 to 60
Rated operational current
I
e
/AC-14
mA
1 to 300
Rated operational voltage
U
e
DC voltage
L/R
200 ms
VDC
3 to 60
Rated operational current
I
e
/DC-13
mA
1 to 300
Transverse auxiliary switch at front with 1 NO + 1 NC, 2 NO contacts
Rated operational voltage
U
e
AC voltage
VAC
24
230
Rated operational current
I
e
/AC-15
A
2
0.5
Rated operational current
I
e
/AC-12
I
th
A
2.5
2.5
Rated operational voltage
U
e
DC voltage
L/R
200 ms
VDC
24
48
60
Rated operational current
I
e
/DC-13
A
1
0.3
0.15
Lateral auxiliary switch with 1 NO + 1 NC, 2 NO, 2 NC, 2 NO + 2 NC and alarm switch
Rated operational voltage
U
e
AC voltage
VAC
24
230
400
690
Rated operational current
I
e
/AC-15
A
6
4
3
1
Rated operational current
I
e
/AC-12
I
th
A
10
10
10
10
Rated operational voltage
U
e
DC voltage
L/R
200 ms
VDC
24
110
220
440
Rated operational current
I
e
A
2
0,5
0.25
0.1