3RT1/3RH1 contactors
SIRIUS System Manual
3-124
GWA 4NEB 430 0999-02b
3RT13 contactors, 4-pole (4 NO contacts), for switching resistive loads
1) Corresponds to section from IEC 60 947-4 (VDE 0660 Part 102):
Coordination type "1":
The destruction of the contactor and the overload relay is permissible. The contactor and/or overload relay must be replaced, if necessary.
Coordination type "2":
The overload relay must not be damaged. Contact welding on the contactor is permissible, if it can be easily separated again from the contactor.
2) Test conditions in acc. with IEC 90 947-4-1.
3RT14 contactors, 3-pole
Contactor
Frame size
Type
S3
3RT14 46
Utilization categories DC-3 and DC-5, shunt and series motors
Number of conducting paths in series connection
1
2
3
Rated operational currents
I
e
(at 60 °C)
Up to 24 V
60 V
110 V
A
A
A
6
3
1.25
130
130
130
130
130
130
220 V
440 V
600 V
A
A
A
0.35
0.15
0.1
1.75
0.42
0.27
4
0.8
0.45
Power loss per conducting path
At
I
e
/AC-1
W
12.5
Technical specifications
Contactor
Frame size
Type
S00
3RT13 16/17
S0
3RT13 25/26
S2
3RT13 36
S3
3RT13 44
S3
3RT13 46
General specifications
Mechanical life
Opera-
ting
cycles
30 mill.
10 mill.
Electrical service life with Ie/AC-1
Opera-
ting
cycles
Approx. 0.5
mill.
Rated insulation voltage Ui
(pollution degree 3)
V
690
Permissible ambient temperature
For operation
During storage
°C
°C
–25 to +60
–55 to +80
Degree of protection
in acc. with IEC 60 947-1 and
DIN 40 050
Terminal housing
IP20
IP 20
IP 00
Short-circuit protection for contactors without overload relay
Main circuit
Fuse-links, performance class gL/gG
NH type 3NA,
DIAZED type 5SB,
NEOZED type 5SE
– In acc. with IEC 60 947-4/
DIN EN 60 947-4 (VDE 0660 Part 102)
Coord. type "1"
1
)
A
35
63
160
250
250
Coord. type "2"
1
)
A
20
25/35
63
125
160
Unwelded
2
)
A
10
16
50
63
100
Drive
Operating range of the magnet coils
AC
At 50 Hz:
0.8 - 1.1 x U
s
AC/DC: 0.8 - 1.1 x
U
s
At 60 Hz:
0.85 - 1.1 x U
s
DC
At +50 °C: 0.8 - 1.1 x U
s
At +60 °C: 0.85 - 1.1 x U
s
Power input of the magnet coils
(cold coil and at 1.0 x
U
s
)
AC operation
Hz
50/60
50
50/60
50
50/60
50
50/60
Making capacity
cos
ϕ
VA
26.5/24.3
0.79/0.75
61
0.82
64/
63
0.82
0.74
145
0.79
170/
155
0.76/
0.72
270
0.68
298/
274
0.72/
0.62
Holding power
cos
ϕ
VA
4.4/3.4
0.27/0.27
7.8
0.24
8.4/
6.8
0.24/
0.28
12.5
0.36
15/
11.8
0.35/
0.38
22
0.27
27/
20
0.29/
0.31
DC operation
Making capacity = holding power
W
3.3
5.6
13.3
15
Содержание SIRIUS