Operating principle of Soft torque during stopping
The Soft Torque function enables the motor to coast down smoothly at an almost constant rate
of deceleration. Ensuring that the motor coasts down smoothly is particularly useful for
stopping pumps in order to prevent water hammers in the connected piping. The Soft Torque
function for stopping can only be activated when a stopping time of more than 3 seconds is set.
Speed curve
Q>PLQ
@
Q
1
W>V@
n
N
Rated motor speed
①
Motor speed with Soft Torque
②
Motor speed without Soft Torque
8.7
Functions under "Additional parameters"
Operating principle
The 3RW51 soft starter has additional functions and settable parameters that are to be found
under "Additional parameters" in the 3RW5 HMI High Feature.
Setting options
• 3RW5 HMI High Feature (accessory)
Access protection to 3RW5 HMI High Feature is not active or has been reset.
Menu: "Parameters > Soft Starter > Additional parameters"
• You can find additional setting options, if they exist, in the associated chapter of the
respective parameter.
Functions
8.7 Functions under "Additional parameters"
SIRIUS 3RW51 Soft Starter
Equipment Manual, 09/2020, A5E37108631002A/RS-AC/003
99
Содержание SIRIUS 3RW51
Страница 8: ...Table of contents SIRIUS 3RW51 Soft Starter 8 Equipment Manual 09 2020 A5E37108631002A RS AC 003 ...
Страница 32: ...Description 3 10 Accessories SIRIUS 3RW51 Soft Starter 32 Equipment Manual 09 2020 A5E37108631002A RS AC 003 ...
Страница 128: ...Functions 8 12 3RW5 HMI High Feature SIRIUS 3RW51 Soft Starter 128 Equipment Manual 09 2020 A5E37108631002A RS AC 003 ...
Страница 166: ...Circuit diagrams 13 1 CAx data SIRIUS 3RW51 Soft Starter 166 Equipment Manual 09 2020 A5E37108631002A RS AC 003 ...
Страница 208: ...Glossary SIRIUS 3RW51 Soft Starter 208 Equipment Manual 09 2020 A5E37108631002A RS AC 003 ...
Страница 210: ...Index SIRIUS 3RW51 Soft Starter 210 Equipment Manual 09 2020 A5E37108631002A RS AC 003 ...