6. Change the setting of the selected parameter using the RESET / TEST key.
You can recognize your selection by the color combination of the three LEDs RN, ER and MT.
Setting the parameter "Control via digital input" (selection in Step 1):
Control via digital input / response to bus errors
"RN" LED
"ER" LED
"MT" LED
Set parameter value
Off
Off
Off
Manual activation
Off
Off
Lights up yel‐
low
Permanent activation
Off
Lights up red
Lights up yel‐
low
Activate on bus error (factory setting)
Lights up green
Lights up red
Lights up yel‐
low
No change on bus error
Setting of the parameter "Output ON / RUN" (selection in Step 1):
Output ON / RUN
"RN" LED
"ER" LED
"MT" LED
Set parameter value
Off
Off
Off
Output function ON
Off
Off
Lights up yel‐
low
Output function RUN
7. Switch off the power supply (control supply voltage) of the 3RW51 soft starter for at least
5 seconds.
The set parameters and parameter values are stored.
8. Switch on the power supply (control supply voltage) of the 3RW51 soft starter again.
The set parameters and parameter values are now active.
Further parameterization options
• 3RW5 HMI High Feature (accessory)
– Menu: "Parameters > Soft Starter > Additional parameters > Control via digital input"
(3RW5 HMI High Feature with firmware version V3.0 and higher)
– Menu: "Parameters > Soft Starter > ON / RUN relay output"
• Procedure in chapter Parameterizing output 13 / 14 (Output signal ON or RUN) (Page 78)
Parameter assignment
6.8 Parameterize the response to bus errors and output 13, 14 (ON /
SIRIUS 3RW51 Soft Starter
Equipment Manual, 09/2020, A5E37108631002A/RS-AC/003
81
Содержание SIRIUS 3RW51
Страница 8: ...Table of contents SIRIUS 3RW51 Soft Starter 8 Equipment Manual 09 2020 A5E37108631002A RS AC 003 ...
Страница 32: ...Description 3 10 Accessories SIRIUS 3RW51 Soft Starter 32 Equipment Manual 09 2020 A5E37108631002A RS AC 003 ...
Страница 128: ...Functions 8 12 3RW5 HMI High Feature SIRIUS 3RW51 Soft Starter 128 Equipment Manual 09 2020 A5E37108631002A RS AC 003 ...
Страница 166: ...Circuit diagrams 13 1 CAx data SIRIUS 3RW51 Soft Starter 166 Equipment Manual 09 2020 A5E37108631002A RS AC 003 ...
Страница 208: ...Glossary SIRIUS 3RW51 Soft Starter 208 Equipment Manual 09 2020 A5E37108631002A RS AC 003 ...
Страница 210: ...Index SIRIUS 3RW51 Soft Starter 210 Equipment Manual 09 2020 A5E37108631002A RS AC 003 ...