Ramp-down time
U
N
Line voltage
Parameters
Parameter
Description
Stopping time
The length of the stopping time defines the time within which the motor volt‐
age is reduced from line voltage to 0 V. It may take longer for the motor to
actually coast down to a standstill.
The setting "0 s" causes the motor to be shut down immediately without a down
ramp.
• Factory setting: 0 s
• Setting range: 0 ... 20 s
8.4
Motor protection
8.4.1
Electronic motor overload protection
The 3RW51 soft starter has an integrated motor protection, which is available even when the
soft starter is bypassed with the external contactor.
Functions
8.4 Motor protection
SIRIUS 3RW51 Soft Starter
Equipment Manual, 09/2020, A5E37108631002A/RS-AC/003
95