Error
No.
1)
Error
Cause
Remedy
RESET MODE
Man‐
ual
2)
Re‐
mote
3)
Auto
4)
1523
Device error
Irrecoverable error detec‐
ted following self-diag‐
nostics (self-test, contac‐
tor contacts, switching el‐
ement, etc.).
Switch off the power supply
(control supply voltage) for at
least 5 seconds and switch it on
again. If the device error is still
present proceed as follows:
• Please contact Technical
Support (Support Request
(Page 11)).
• Replace the device.
-
-
-
1605
Line voltage for test re‐
quired
• The power switch or
the power supply is
not correctly connec‐
ted.
• No current
Check the cables and the cable
connections and replace any
defective components.
x
x
-
1755
Operating temperature
too high
The temperature in the
components has excee‐
ded the highest permissi‐
ble limit.
Check the ambient tempera‐
ture or the control cabinet ven‐
tilation.
-
-
x
1)
Visible on the display of the 3RW5 HMI Standard.
2)
Acknowledgment via Manual RESET.
3)
Acknowledgment via Remote RESET.
4)
Acknowledgment via Auto RESET.
5)
Acknowledgment depends on parameter RESET MODE.
9.5
Faults and remedial actions on the 3RW5 HMI High Feature
Display of the faults on the 3RW5 HMI High Feature
Detailed information about faults and remedial actions appears in plain text on the display.
Faults and remedial actions
Error
Cause
Remedy
Error HMI
Unrecoverable error detected af‐
ter internal diagnostics (self-test,
etc.).
Replace the device.
FW update not successful
The firmware is incomplete
and/or the firmware expansions
are incomplete or incompatible.
• Run a complete firmware update.
• Check any error messages that occur.
• Check to see whether or not the firmware update
was aborted.
Messages & diagnostics
9.5 Faults and remedial actions on the 3RW5 HMI High Feature
SIRIUS 3RW51 Soft Starter
Equipment Manual, 09/2020, A5E37108631002A/RS-AC/003
139
Содержание SIRIUS 3RW51
Страница 8: ...Table of contents SIRIUS 3RW51 Soft Starter 8 Equipment Manual 09 2020 A5E37108631002A RS AC 003 ...
Страница 32: ...Description 3 10 Accessories SIRIUS 3RW51 Soft Starter 32 Equipment Manual 09 2020 A5E37108631002A RS AC 003 ...
Страница 128: ...Functions 8 12 3RW5 HMI High Feature SIRIUS 3RW51 Soft Starter 128 Equipment Manual 09 2020 A5E37108631002A RS AC 003 ...
Страница 166: ...Circuit diagrams 13 1 CAx data SIRIUS 3RW51 Soft Starter 166 Equipment Manual 09 2020 A5E37108631002A RS AC 003 ...
Страница 208: ...Glossary SIRIUS 3RW51 Soft Starter 208 Equipment Manual 09 2020 A5E37108631002A RS AC 003 ...
Страница 210: ...Index SIRIUS 3RW51 Soft Starter 210 Equipment Manual 09 2020 A5E37108631002A RS AC 003 ...