SIRIUS 3RR2 current monitoring relays
8.8 Operation
SIRIUS Innovations
System Manual, 01/2011, A8E56203870002-03
725
Load current monitoring (apparent current/active current)
Definition of load current monitoring
The relays monitor an AC load current which flows through the device terminals depending
on whether monitoring has been set to check for overshoot or undershoot, or window
monitoring.
There are two ways of monitoring the load current:
●
Apparent current I
s
●
Active currentI
p
Explanation
Whereas apparent current monitoring is primarily used in the rated torque range or for
overload, active current monitoring can be used to observe and evaluate the degree of
loading across a motor's entire torque range.
FRV˳
/$$$=N:1P
,>$@
,S ,V[FRV˳
,V
FRV˳
0>@
①
Strong change in cos φ
②
Strong change in apparent current
cos φ
Power factor
I [A]
Current
M [%]
Torque as a % of the rated torque
I
p
Active current
I
s
Apparent current
Figure 8-5
Load current monitoring diagram
The diagram shows that it only makes sense to use the power factor cos φ to monitor the
rated current up to approx. 70%. At a higher rated current the change in the power factor is
too slight to produce measured values of any significance. In contrast, the monitoring quality
of the apparent current I
s
increases along with the torque, in other words as the rated current
rises. It is for this reason that monitoring of the apparent current is primarily used if a load
needs to be protected against overload. Integrated monitoring from no-load operation up to
overload is only possible by monitoring the active current I
p
, the product of power factor and
apparent current.
Factory setting
Load current monitoring is factory-set to apparent current monitoring I
s
.
Содержание SIRIUS 3RH Series
Страница 1: ...SIRIUS Innovations System Manual 01 2011 Industrial Controls Answers for industry ...
Страница 2: ......
Страница 640: ...SIRIUS 3RA21 22 load feeders 6 12 Circuit diagrams SIRIUS Innovations 640 System Manual 01 2011 A8E56203870002 03 ...
Страница 760: ...Appendix A A 3 Correction sheet SIRIUS Innovations 760 System Manual 01 2011 A8E56203870002 03 ...
Страница 785: ......