SIRIUS 3RR2 current monitoring relays
8.8 Operation
SIRIUS Innovations
710
System Manual, 01/2011, A8E56203870002-03
8.8.1.7
Diagnostics with LED
Status display
On the analog setting current monitoring relay, two status LEDs indicate the operating state:
●
FAULT (red)
●
READY (green)
Display
Meaning
FAULT off
Measured value is within range limits
FAULT steady on
Device has tripped
FAULT flashing slowly
Delay time is running
FAULT flashing rapidly
Cable break/phase failure detected
READY off
No voltage at B1 - B2
READY on
Voltage at B1 - B2
You will find more information about the LED display and its various settings in the chapter
titled Function charts for Basic analog setting current monitoring relay (Page 692).
Cable break detected
The CO contact responds immediately when a cable break is detected (only residual current
in branch circuit 1L1/2T1 or 3L2/4T2). All running delay times are aborted and the red
FAULT LED flashes rapidly. If the load current in both circuits falls below the lower range
limit, the current monitoring relay responds again in accordance with the settings made. If
Memory = I, the tripping state is saved.
Содержание SIRIUS 3RH Series
Страница 1: ...SIRIUS Innovations System Manual 01 2011 Industrial Controls Answers for industry ...
Страница 2: ......
Страница 640: ...SIRIUS 3RA21 22 load feeders 6 12 Circuit diagrams SIRIUS Innovations 640 System Manual 01 2011 A8E56203870002 03 ...
Страница 760: ...Appendix A A 3 Correction sheet SIRIUS Innovations 760 System Manual 01 2011 A8E56203870002 03 ...
Страница 785: ......