4.9.5
Auxiliary release
4.9.5.1
Description
Auxiliary release
The releases, which are not size-specific, are available in three versions:
●
Undervoltage release
●
Undervoltage release with leading auxiliary contacts (2 NO contacts)
●
Shunt release
The releases are mounted on the right-hand side of the motor starter protector and have a
width of 18 mm. They are available for all commonly used voltages all over the world. They
can be installed inside molded-plastic enclosures.
Note
One auxiliary release can be mounted on each motor starter protector.
No accessories can be mounted on the right-hand side of 3RV21 motor starter protectors
with overload relay function.
Shunt release
For remote-controlled tripping of the motor starter protector
●
Via PLC: The release's coil should only be energized for a brief period.
Undervoltage release
The undervoltage release trips the motor starter protector in the event of voltage interruption
(e.g. if the power supply fails) and prevents the motor from being unintentionally restarted
when the voltage is restored. The motor starter protector then has to be reclosed by hand.
Particularly suitable for EMERGENCY OFF disconnection via corresponding EMERGENCY
OFF pushbutton according to IEC 60204-1 (VDE 0113)
Содержание SIRIUS 3RH Series
Страница 1: ...SIRIUS Innovations System Manual 01 2011 Industrial Controls Answers for industry ...
Страница 2: ......
Страница 640: ...SIRIUS 3RA21 22 load feeders 6 12 Circuit diagrams SIRIUS Innovations 640 System Manual 01 2011 A8E56203870002 03 ...
Страница 760: ...Appendix A A 3 Correction sheet SIRIUS Innovations 760 System Manual 01 2011 A8E56203870002 03 ...
Страница 785: ......