SIRIUS 3RV2 motor starter protectors
4.6 Mounting
SIRIUS Innovations
System Manual, 01/2011, A8E56203870002-03
401
4.6
Mounting
4.6.1
Standard mounting
4.6.1.1
Minimum clearances and mounting position
Minimum clearances
The following clearances from grounded or live parts and from cable ducts made of molded
plastic must be observed in compliance with IEC 60947-2 when mounting motor starter
protectors.
/
=
59
59
=
<
<
/ /
7 7 7
7 7 7
/ / /
Figure 4-3
Clearances from grounded or live parts
Table 4- 7
Installation guidelines for motor starter protectors
U
e
[V]
Y [mm]
Z [mm]
240
30
9
400
30
9
440
30
9
500
30
9
690
50 / 70
1)
30
1)
Up to and including the setting range of 32 A, the required clearance above and below is 50 mm;
for the 36/40 A setting range, the clearance is 70 mm.
Note
Terminal block type E
In conjunction with type E terminal block 3RV2928-1H the applicable lateral clearance is
30 mm for all voltages.
Mounting position
The mounting position of 3RV2 motor starter protectors can be selected at will.
Содержание SIRIUS 3RH Series
Страница 1: ...SIRIUS Innovations System Manual 01 2011 Industrial Controls Answers for industry ...
Страница 2: ......
Страница 640: ...SIRIUS 3RA21 22 load feeders 6 12 Circuit diagrams SIRIUS Innovations 640 System Manual 01 2011 A8E56203870002 03 ...
Страница 760: ...Appendix A A 3 Correction sheet SIRIUS Innovations 760 System Manual 01 2011 A8E56203870002 03 ...
Страница 785: ......