SIRIUS 3RA28 function modules for mounting on 3RT2 contactors
7.4 Functions
SIRIUS Innovations
654
System Manual, 01/2011, A8E56203870002-03
7.4.2.3
OFF-delay without auxiliary voltage
Contacts
Function modules are available with the following contacts:
3RA2815-.AW10:
1 CO contact
3RA2815-.FW10:
1 NC contact and 1 NO contact
Time ranges
The function modules support time-delayed switching from 0.05 to 100 s.
Function charts
3RA2815-.AW10
≥
200 ms
A1/A2
15/18
15/16
t
3RA2815-.FW10
≥
200 ms
A1/A2
27/28
35/36
t
Method of operation
When the voltage is connected to A1/A2 (contactor), the solid-state time-delay auxiliary
switch (3RA2815) switches the output relay. The operating time t starts when the voltage is
disconnected. The relay switches back to the idle state at the end of the operating time t.
There is an assurance that if the minimum ON duration is not observed either the time lapse
will not start or, if the time lapse has started, it will always be completed in an orderly
fashion. Users can rely on intermediate states of the functional sequence, such as "no relay
dropout", being detected. The minimum ON duration of 200 ms must be observed.
Содержание SIRIUS 3RH Series
Страница 1: ...SIRIUS Innovations System Manual 01 2011 Industrial Controls Answers for industry ...
Страница 2: ......
Страница 640: ...SIRIUS 3RA21 22 load feeders 6 12 Circuit diagrams SIRIUS Innovations 640 System Manual 01 2011 A8E56203870002 03 ...
Страница 760: ...Appendix A A 3 Correction sheet SIRIUS Innovations 760 System Manual 01 2011 A8E56203870002 03 ...
Страница 785: ......