SIRIUS 3RU2/3RB3 overload relays
5.6 Mounting
SIRIUS Innovations
508
System Manual, 01/2011, A8E56203870002-03
5.6
Mounting
5.6.1
Mounting options
Mounting options for the 3RU21
3RU21 thermal overload relays are matched to 3RT contactors in terms of their electrical
and mechanical features. As a result, direct mounting can be achieved easily. Alternatively,
the devices are suitable for stand-alone assembly.
Mounting options for the 3RB30/3RB31
3RB30/3RB31 solid-state overload relays are suitable for space-saving, direct mounting onto
3RT contactors as well as for stand-alone assembly.
5.6.2
Minimum clearances and mounting position
Minimum clearance
A minimum lateral clearance of > 6 mm must be maintained from grounded parts.
Mounting position for 3RU21 thermal overload relay
The diagrams below illustrate the permissible mounting positions for contactor mounting and
stand-alone assembly in the case of 3RU21 thermal overload relays.
Table 5- 13 Permissible mounting positions for the 3RU21
Overload relay, stand-alone assembly
Con overload relay
,H[
,H
,H[
,H[
r
r
The set value is 1.1 times the motor current for a mounting position in the hatched area.
Mounting position for 3RB30/3RB31 solid-state overload relay
For 3RB30/3RB31 solid-state overload relays any mounting position can be chosen as
required.
Содержание SIRIUS 3RH Series
Страница 1: ...SIRIUS Innovations System Manual 01 2011 Industrial Controls Answers for industry ...
Страница 2: ......
Страница 640: ...SIRIUS 3RA21 22 load feeders 6 12 Circuit diagrams SIRIUS Innovations 640 System Manual 01 2011 A8E56203870002 03 ...
Страница 760: ...Appendix A A 3 Correction sheet SIRIUS Innovations 760 System Manual 01 2011 A8E56203870002 03 ...
Страница 785: ......